58
Operation Manual
FT1020G3 Rev 2.10.4
Example; pre-warning zone 123, address 45 (within zone 123):
"
SMOKE
" after the presentation number is automatically added depending on the type of
alarm point (i.e. SMOKE, HEAT, MULTI or MCP).
Note:
The text "Menu" for the soft key “P5” is visible in the display, only if the door in the
FDCIE is open.
If more than one pre-warning is activated, the LEDs "SEVERAL ALARMS" (L6) are blinking
and the pre-warnings will be automatically scrolled (every five seconds). Pre-warnings are
automatically reset, see chapter "Alarm reset", page 68.
15.2
Fire Alarm
The FT1020G3 system can support up to 15360 fire alarms but only 512 fire alarms can
be presented in the FDCIE display. If more than 512 fire alarms are activated, no additional
fire alarms can be displayed until one or more of the first 512 fire alarms are reset.
Normally all fire alarms will be presented in all control units (default) but it is possible to
have selective alarm presentation, i.e. only fire alarms from selected Control Units will be
presented in the Control Unit, set in EBLWin for each Control Unit.
See also chapter "The information area priority order", page 22.
The following will occur in case of a fire alarm:
•
The buzzer in the FDCIE sounds 0.4 sec. each 0.4
th
sec. (0.4 / 0.4 sec.).
•
LEDs "Fire" (L1) are blinking (0.4 / 0.4 sec.).
•
Output for routing equipment (Fire brigade TX) and outputs type "Routing
equipment" are activated.
•
Programmable outputs for fire alarm are activated
•
In the FT1020G3 display, a presentation number (zone/address) with a user
definable text message (if programmed) will be shown (for the first fire alarm).
•
Some additional information is also presented in the FDCIE display.
One alarm point activating fire alarm.
30
Outputs programmed for General fire alarm and outputs programmed for the activated fire alarm(s).
Pre-
warning
123-45
SMOKE
User definable alarm text for 123-45
Zone
Address
Menu
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...