82
Operation Manual
FT1020G3 Rev 2.10.4
FAULT: Supervised output x, Control Unit xx 5010
If the output is programmed for
sounders
or
OWS
(type "Alarm
devices"), it is also indicated by LED Fault / Disablements" Alarm
devices" blinking.
If the output is programmed for Fire Brigade TX (type "Routing
equipment"), it is also indicated by LED Fault / Disablements" Fire
brigade TX" blinking.
If the output is programmed for an extinguishing system (type
"Extinguishing"), there will be an additional information text close to the
soft key area in the display:
Extinguishing wire fault
.
•
x=0
(S0): Short circuit/break on the connected cable/ equipment
and/or blown fuse F4 on the main board.
•
x=1
(S1): Short circuit/break on the connected cable/ equipment
and/or blown fuse F5 on the main board.
•
x=2
(S2): Short circuit/break on the connected cable/ equipment
and/or blown fuse F6 on the main board.
•
x=3
(S3): Short circuit/break on the connected cable/ equipment
and/or blown fuse F7 on the main board.
Fuse T
500mA
L 250V (TR5).
o
Calibration not performed via menu H5/A1.
o
Connected equipment might be "missing".
o
End of line resistor(s) missing or not the correct value (1-5
resistors 33K)
Note:
The calibrated value has to be in the range 1K-50K.
FAULT: Supervised output x, Control Unit xx 5012
Main board 5012, Supervised (1-
50 kΩ):
x=0 (S0): Short circuit/break on the connected cable/ equipment
x=1 (S1): Short circuit/break on the connected cable/ equipment
x=2 (S2): Short circuit/break on the connected cable/ equipment
x=3 (S3): Short circuit/break on the connected cable/ equipment
Fuse T500mA L 250V
• Calibration not performed via menu H5/A1.
• Connected equipment might be "stolen".
• Resistor(s) missing or not correct value. (1-
5 resistors 33 kΩ)
FAULT: Supervised output x, technical number xxxxxx
This fault message is valid for a COM loop output unit 3364 output or
4464 board output.
If the output is programmed for sounders (type Alarm devices), it is also
indicated by LED Fault / Disablements "Alarm devices" blinking.
If the output is programmed for fire brigade tx (type Routing equipment),
it is also indicated by LED Fault / Disablements "Fire brigade tx"
blinking.
•
Calibration not performed via menu H5/A1. (Valid for 3364 only)
•
Short-circuit / break on the connected cable / equipment.
•
Missing connected equipment.
•
End-of-line capacitor(s) missing or not correct value, 1-5
capacitors (470 nF). (Valid for 3364 only)
•
End-of-line device 4472, or end-of-line resistor, is missing (Valid
for 4464 only)
Note
: The calibrated value has to be in the range 470 nF – 5 x 470 nF
(2350 nF). (Valid for 3364 only)
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...