FAULT: Zone Line Input, Zone xxx Address xx
CU xx Expansion Board x input x
Valid for the 8 zones exp. board 4580 zone line input x (xxx-xx = zone
– address). The board is mounted in Control Unit xx.
Open circuit on the zone line, wrong / no end-of-line device / short-
circuit (if not programmed for fire alarm at short-circuit).
FAULT: Zone Line Input, zone: xxx address: xx
technical number xxxxxx
Valid for the Multipurpose I/O unit 4461 (or 3361) monitored zone line
input Z. open circuit on the zone line or wrong / no end-of-line
capacitor (10 uF) or short-circuit (if not programmed for fire alarm at
short-circuit).
No contact with main board
Shown only in the affected Control Unit.
•
Check that "MMI board" is selected in the SSD (EBLWin
Control unit properties).
•
Fault in the Main board software or hardware. Check the cable
between the Main board and MMI board. It may require system
software download, this will erase SSD. Call for service
technician immediately.
(External fault; User programmable text)
Programmable input is connected to any external equipment's fault
output. User definable fault message (< 40 characters) has to be
programmed via EBLWin.
Note
, the prefix "
FAULT:
" will
not
be automatically added.
FAULT: Corrupt program area 2, Control unit xx
A fault in the control unit xx MMI board. There is some internal fault
on the board
•
Try to download S/W again
•
Replace the MMI board
17.2
Fault Acknowledge
When a fault is generated in FT1020G3, the following may occur:
•
The LEDs
Routing equipment
"Fault TX activated" and
Fault / Disablements
"General fault" are turned on to indicate that the output for routing equipment (Fault
tx) is activated
•
LEDs
Fault / Disablements
"Alarm devices", "System fault" and/or
Fault /
Disablements
"Fire brigade TX" may be turned on as well.
•
Output for routing equipment (Fault TX) is activated.
•
Output for general fault is activated.
•
Output for general charger fault might be activated.
•
One or more fault messages including date and time are shown in the Control Unit
display.
If “Fault latching” is selected in EBLWin (default), once the fault is corrected, the "Serviced"
message will be shown after the time i.e. the fault is already serviced / corrected. When the
“Fault latching” check box is not selected in EBLWin, the “Serviced” fault will automatically
disappear from the list.
Any already acknowledged fault in the list is indicated by “
Acknowledged
”.
Example: Fault messages shown in the Control Unit display:
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...