Figure 14 1205 Zone Control Module
5.4.3
Fan / Damper Control Module 1206 / 1211
The
1206
is a four Fan Display and Control Module which is an upgrade over the old 4582
/ SUB902 Fan Display combination. The 1206 is programmed in EBLWin as an “I/O Matrix
board 4582” for “Fan / Damper Control”.
The
1211
is a new four Damper Display and Control module utilising the same 1206 PCB
but with different label and functionality, it is intended to control fire dampers. The 1211 is
programmed in EBLWin as an I/O Matrix board 4582 for “Fan / Damper Control”.
Each 1206 and 1211 Require 2 x 10HP (100 mm) space on the ancillary rack. 1206 and
1211 can connect to any COM loop 0-3, refer to the limitations of 4582 shown in Table 3
page 16.
Figure 15 1206 / 1211 Fan / Damper Control Module
Each fan / damper control module consists of an I/O matrix 4582 circuit and controls /
indications integrated in one PCB specifically configured to provide fan or damper control
and indications. Each module can control and indicate the status of up to 4 different fans
or dampers. Up to 24 x fan / damper control modules can be used to provide 96 fan or
damper interfaces if no other Expansion Boards 458X or zone modules.
Note:
The total number of fan / damper modules must be reduced by one for every other
option fitted, e.g. zone module, generic module, Expansion Board, etc.
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...