Technical/Programming Manual
FT1020G3 Rev 2.2.1
20
Figure 5 FT1020G3 front display
The
CP
is used to "communicate" with the system, i.e. for commissioning, routine tests,
maintenance, etc. Access codes for different access levels are required. A keypad is used
to get access to the system (a menu tree with main and sub menus) and for operational
control of the system. Up to ten
User names
can be used for three different
User level
types
. A
Password
(six digits) for each User name is required
19
.
The CP has several system status LEDs and a keypad.
Note:
Regarding LED indicators, keypad / push buttons / soft keys, user level types and
for more information, see FT1020G3 Operation Manual.
Each FT1020G3 Control Unit has the following basic configuration:
Oyster metal cabinet with acrylic door
MMI board (5011), see drawing F727
FT1020G3 front with display
Main board (5010), see drawing F726
Four COM loops (0-3) to which the loop units are connected, for
connections and more information, see drawing F784-01, F784-02 and
F733.
Four programmable supervised voltage outputs (S0-S3), for connections
and more information, see drawing F732-02.
Two programmable relay outputs (R0-R1), for connections and more
information, see drawing. F732-02.
Four programmable inputs (I0-I3)
20
, for connections and more information,
see drawing F732-02.
19
The same User names and Passwords (for the different user levels) can be used for logon to the Web-server.
20
In NZ convention, only I
1
, I
2
and I
3
are available i.e. Input I
0
cannot be used