Technical/Programming Manual
FT1020G3 Rev 2.2.1
54
Figure 24 EBLWin properties dialog box for 4301 / 4401(Normal Mode)
9.1.1.1
Analogue Sensor Bases (ASB)
An Analogue detector (Sensor) to be plugged in an Analogue base. The COM loop address
is set in the detector, see below.
3312
Analogue Base 3312 has screw terminals for the COM loop and an RIL. Prepared
for mechanical lock of the detector - if required. Recess for label holder (3391).
The base has an address label on which the plugged-in detector's COM loop
address can be written.
4313
Analogue Base with isolator. An Analogue detector (Sensor) is to be plugged in
4313. Terminals are provided for remote indicators (RIL). Prepared for mechanical
lock of the detector - if required. Recess for label holder (3391). It has also a built-
in short circuit isolator (see page 64). The isolator's COM loop address is set with
the Address setting tool 3314 / 4414. The base has an address label on which both
the plugged-in detector's COM loop address and the isolator's COM loop address
can be written.
The Address setting tool 3314 / 4414 is also used for mode setting:
NORMAL mode
: Used for 4313 in system FT1020G3.
9.1.1.2
Addressable Manual Call Points
4433
Addressable Manual Call Point
47
with isolator. Conforms to EN54-11, replaces
3333. This MCP is similar to 3333 but it also has a built-in short circuit isolator. A
built-in LED will indicate that a fire alarm is generated, i.e. the glass is broken.
Routine testing can be performed with a supplied test key, without breaking the
glass. A hinged polycarbonate flap protects the glass from accidental triggering.
The COM loop address is set with the Address setting tool 3314 / 4414.
The isolator does not use any COM loop address
4433 is to be surface mounted in the supplied red back box or flush mounted as it
is mounted in the FT1020G3 cabinet.
For indoor use and in dry premises.
The Address setting tool 3314 / 4414 are also used for mode setting:
47
The manual call points have a response time < 5 s