Technical/Programming Manual
FT1020G3 Rev 2.2.1
78
26. Pre-warning, e.g. from a High Sensitive Smoke Detector's pre-warning output.
Zone no. and Address set to the same as the corresponding fire alarm (from the
same detector).
27. A technical warning is neither an alarm nor a fault. It is activated as long as the
input is activated, which is indicated by a blinking symbol
in the display.
Identified via menu H4/U6. Output with trigger condition "Technical warning
(+name)" will be activated.
28. The Addressable multipurpose I/O unit 3361 monitored Input
“In0” used as zone
line input (Z)
for conventional detectors. Use End-of-Line capacitor with
value 470nF.
11.2
Logic
The logic has to be set
(in EBLWin dialog box “properties”).
11.2.1
Non-Supervised (Default)
(•) Normally open / Normally low,
normally open contact or normally low opto-
coupler input (3361).
( ) Normally closed / Normally high,
normally closed contact or normally high opto-
coupler input (3361).
11.2.2
Supervised
Valid for the Inputs and Outputs of the expansion board 4583 programmable inputs (Input
0-4) only.
(•) Normally open (high resistance)
( ) Normally closed (low resistance)
Depending on the selected logic, Normally Open (high resistance, 3K3)
or
Normally Closed
(low resistance, 680R), the function will be according to the Table 10 on page 73.