Technical/Programming Manual
FT1020G3 Rev 2.2.1
83
13
Output programming
Output programming is done in EBLWin. See the EBLWin dialog box.
13.1
Type of output
Some output types can be collectively disabled, some others can be indicated by an LED
when activated. The following types are available (numbering only for the comments
below):
1.
Control
2.
Fire Ventilation
3.
Extinguishing
4.
Alarm Device
5.
Routing equipment
(Fire brigade TX)
6.
Control, neutral
7.
Interlocking
Comments to the output types:
1. Default. General (normal) control output
88
2. Used to activate fire ventilation equipment 88
3. Used to activate extinguishing equipment 88
4. Used for sounders or OWS, etc.
91
5. Used for
fire brigade TX
outputs only
92
6. General (normal) control output. No collective disablement and no LED
indication.
7. This output 88 can be used together with a corresponding Interlocking input.
See chapter "Interlocking function", page 96. Activated output is shown in
menu H9/C1.
13.2
Logic
(•) Normally open / low,
Normally Open relay contact or normally low voltage output.
93
( ) Normally closed / high,
Normally Closed relay contact or normally high voltage output
(24V DC).
94
88
Controlled by menu H2/B3 Disable / Re-enable output type.
89
Activated output is indicated by the LED "Ventilation". (Feedback from the fire ventilation equipment to a programmable input
can instead light up the LED).
90
Activated output is indicated by the LED "Extinguishing". (Feedback from the fire extinguishing equipment to a programmable
input can instead light up the LED).
91
Controlled by menu H2/B4 Disable / Re-enable Alarm devices and by push button "Silence alarm devices" on the control unit
front. Output fault / disabled is indicated by LED
Fault / Disablements
"Alarm devices" blinking / continuous on.
92
Activated according to its control expression (trigger condition 43
Indication Fire brigade TX activated
must
not
be used).
Disabled similar to the standard control unit "Fire brigade TX" relay output. Activated output is indicated by the LED "Fire
brigade TX". (Feedback from the Fire brigade TX to a programmable input can instead light up the LED). Output fault / dis abled
is indicated by LED
Fault / Disablements
"Fire brigade TX" blinking / continuous on.
NOTE!
When the Alert Annunciation function is to be used, the following trigger condition has to be added to the control
expression:
& !Alert Annunciation activated
. ("&!" is the same as "and not").
93
The logic is set in the EBLWin dialog box "Voltage / Relayed Output".
94
The logic is set in the EBLWin dialog box "Voltage / Relayed Output".
NOTE!
A normally high output cannot be supervised and it will be low for a few seconds during restart of the C.I.E.