Operation Manual
FT128 Rev 2.4
103
"Return"
Start Sensor : 00-00
Write the presentation
number and/or press "A"
to accept or press
"Return" to menu U3.
"Return"
Sensor values
ACCEPT? U3
Scroll or press "Return" to
menu H4. Scroll or press
"Return".
"Return"
Present system status
ACCEPT? H4
Scroll or press "Return".
When scrolling the message "Please Wait….." might be shown
23.3.1
Explanation of the Sensor Values
Momentary
: Momentary value in this menu will be updated following every detector
polling, i.e. approx. every 6 second.
Weekly in NORMAL mode:
The very first week average sensor value for a new installed
detector type 430x and 440x in NORMAL mode is calculated within 2½ minutes after SSD
download & restart. During these 2½ minutes, no fire alarm can be activated and "Weekly:
00.0%/m" will be shown. The "Weekly" value will thereafter be updated every week.
Weekly in Advanced mode
: For the 440x detectors in Advanced mode, the "Weekly"
value is 00.0%/m on delivery. It will be updated during the first 13 minutes when the
detector has been installed. It will thereafter be calculated every 13th minute but will then
only be changed downwards if required. After 18 hours it can be changed downwards or
upwards and after additional 18 hours (36 hours in all) it can be changed downwards or
upwards and it is also saved in the detector's EEPROM, i.e. that value will be used after
the detector loses power. The "Weekly" value for the 440x detectors in Advanced mode is
also called the "Contamination Compensation Value (CCV).
Performance Factor
: The "Performance factor" and "Min. / Max." values are updated each
night (00:00), i.e. the values shown are from the previous day. For more information on
performance factor, see the Planning instructions for the system.
The Performance factor can be 0.00 – 2.55. How the Performance factor (PF) is calculated
is shown to the left.
In an "unstable" environment the Performance factor will be higher than 0.00. This could
for example be the case in a factory (e.g. "dirty" activities during working hours – no or
clean activities during the night) and is not a problem as long as there are no nuisance
(false) alarms or other problems.
Algorithm
: displays the algorithm that is currently in use.
23.3.2
Algorithms
The following table showing the algorithms and the abbreviations respectively:
Algorithm – Normal mode
Detectors 3308/3309, 430x and 440x, all in Normal mode.
Abbreviation
Normal sensitivity (3%) & Normal detection (15 s)
N-15
High sensitivity (2.4%) & Normal detection (15 s)
H-15
Low sensitivity (3.6%) & Normal detection (15 s)
L-15
Normal sensitivity (3%)
& Slow detection (35 s)
N-35
High sensitivity (2.4%) & Slow detection (35 s)
H-35
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...