Operation Manual
FT128 Rev 2.4
111
24.2
Sensitive Fault Detection Mode (H5/A2)
To increase the possibilities to detect faults during commissioning, it is possible to use the
"Sensitive fault detection mode". The time delay for each fault will then be reduced, i.e.
you might find some faults now instead of later.
The activated "Sensitive fault detection mode" is indicated by the LED Routing equipment
"Fault tx activated" and the "Fault" output for routing equipment is "activated".
Note: The "Fault" output for routing equipment is also "activated".
Action
Text in display
Comments
"Access"
Log on to FT128 as shown
in page 35.
Scroll to menu H5
Service
ACCEPT? H5
"A"
Calibration of supervised outputs
ACCEPT? A1
Scroll to menu A2
Sensitive fault detection mode
ACCEPT? A2
"A"
Sensitive fault detection mode is not active
Press ACCEPT to activate
The text shown depends
on the actual status.
Press "A" to accept or
press “Return” to menu A2.
Sensitive fault detection mode is active
Press ACCEPT to deactivate
"Return"
Sensitive fault detection mode
ACCEPT? A2
Scroll or press "Return" to
H5.
"Return"
Service
ACCEPT? H5
Scroll or press "Return"
Note: Don’t forget to turn this mode off after commissioning.
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...