Operation Manual
FT128 Rev 2.4
114
24.5
Display Current Consumption on COM-Loop (H5/A5)
An average current consumption value can be displayed for the COM loop.
Note: No or very small current consumption (< 10mA) will not be presented correctly /
precisely since the accuracy is ± 5 mA.
Action
Text in display
Comments
"Access"
Log on to FT128 as shown
in page 35.
Scroll to menu H5.
Service
ACCEPT? H5
"A"
Calibration of supervised outputs
ACCEPT? A1
Scroll to menu A5
Display current consumption on
COM loop ACCEPT? A5
"A"
Current consumption on COM-loop is
XXX mA ACCEPT?
"A" or
"Return"
Display current consumption on
COM loop ACCEPT? A5
Scroll or press "Return" to
H5.
"Return"
Service
ACCEPT? H5
Scroll or press "Return".
Note: Each window is updated continuously.