24.7
Activate Address Setting Mode for DU (H5/A7)
This function can be used by commissioning / service engineer to activate the address
setting mode in the following
D
isplay
U
nits connected to the RS485 interface in FT128:
•
External Presentation unit (EPU) 1728
•
Alert Annunciation unit (AAU) 1736
A specific unit or all units can be activated for address setting.
Note: The units have to be in operation and in quiescent condition, i.e. the units have
already been addressed.
Action
Text in display
Comments
"Access"
Log on to FT128 as shown
in page 35.
Scroll to menu H5.
Service
ACCEPT? H5
"A"
Calibration of supervised outputs
ACCEPT? A1
Scroll to menu A7
Activate address setting mode for DU
ACCEPT? A7
"A"
Activate address setting mode for DU 0
(9 = All) ACCEPT?
Write the unit's address (0-
7). 9 = All units.
Press "A" to accept.
e.g. "9"
"A"
Operation failed!
If the address setting mode
was not activated.
e.g. "9"
"A"
All DU set in address setting mode
The address has now to be
set / changed in the DU
respectively.
"Return"
Activate address setting mode for DU
ACCEPT? A7
Scroll or press "Return" to
H5.
"Return"
Service
ACCEPT? H5
Scroll or press "Return"
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...