Operation Manual
FT128 Rev 2.4
117
24.8
Setup Wireless Detectors (H5/A8)
This function can be used by commissioning / service engineer to set a Base station for
wireless units 4620 to one of the following modes:
Register:
in order to register one or more wireless detectors 4611 to the Base station
Unregister
: in order to unregister one or more wireless detectors 4611 from the Base
station
Install
: in order to change the normal communication time from every 2
nd
minute to every
5
th
second, to be used during commissioning, etc.
Note:
To set the Base station to any of the modes above, the Base station has to be in a
"Normal state" i.e. not set to any of the modes. For example, a Base station set to e.g.
"Register" mode has to be set back to "Normal state" before it can be set to any other
mode.
For more information, refer to the manual for Wireless Units for Addressable FDCIEs.
Note: The procedure to set a Base station to the "Unregister" and "Install" mode
respectively (and back to the "Normal state") is the same as for the "Register" mode.
Action
Text in display
Comments
"Access"
Log on to FT128 as
shown in page 35.
Scroll to menu H5.
Service
ACCEPT? H5
"A"
Calibration of supervised outputs
ACCEPT? A1
Scroll to menu A8
Setup wireless detectors
ACCEPT? A8
"A"
Set base station mode 000 to mode 0
(0=Register, 1=Unregister, 2=Install)
Write technical
address for the base
station, e.g. "001"
and mode, e.g. “0”
Set base station mode 001 to mode 0
(0=Register, 1=Unregister, 2=Install)
Press "A" to accept.
"A"
Base station 001 set in register mode
"A"
Set base station mode 001 to mode 0
(0=Register, 1=Unregister, 2=Install)
If more base stations shall
be set, continue like
above. If not, press
"Return" to menu A8.
"Return"
Setup wireless detectors
ACCEPT? A8
Scroll or press "Return" to
menu H2.
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...