27.5
Restore Weekly Average to Default (H8/S5)
Valid only for 430x, 4400 and 4401 sensors in NORMAL mode.
If a sensor (analogue smoke detector) is replaced without having generated SERVICE
signal, its week average sensor value has to be cleared and set to the default value (i.e.
"1" = 0.1 %/m), otherwise the new / clean sensor will inherit the old sensor's value.
The week average sensor value has to be restored for each replaced sensor individually.
First replace the sensor then restore the week average sensor value as soon as possible.
Note: First replace the sensor and then clear the week average value as soon as
possible. Authorised service personnel only, must do this. Used incorrectly it can cause
nuisance fire alarms.
The first week average sensor value (after clearing) will be calculated within one hour, then
each week.
Action
Text in display
Comments
"Access"
Log on to FT128 as
shown in page 35.
Scroll to menu H8.
Maintenance
ACCEPT? H8
"A"
Disconnect / Re-connect COM loop
ACCEPT? S1
Scroll to menu S5.
Restore weekly average to default
ACCEPT? S5
"A"
Enter zone-address to restore: 00-00
ACCEPT?
Write the zone-address
and press "A" to accept.
E.g. "01-01"
"A"
Sensor 01-01 (tech addr 001) is restored
to default average
"A"
Enter zone-address to restore: 00-00
ACCEPT?
If more sensors shall be
restored, continue like
above. If not, press
"Return" to menu S5.
"Return"
Restore weekly average to default
ACCEPT? S5
Scroll or press "Return"
to menu H8.
"Return"
Maintenance
ACCEPT? H8
Scroll or press "Return".
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...