Operation Manual
FT128 Rev 2.4
128
27.6
Test of Alarm Devices (H8/S6)
The programmable outputs
of type "Alarm device" can be collectively activated via this
sub menu (S6), which enables the service technician to test the alarm devices without too
much disturbance on site.
The test cannot be started if fire alarm is already activated in FT128
When the test starts, the alarm devices will sound for approx. 1 seconds, be silent for
approx. 29 seconds, sound for approx. 1 seconds and so on.
Note:
Disabled (and silenced) alarm devices will also be tested. The test will continue
for one hour if not stopped via this menu (H8/S6) or if a fire alarm is activated in the
system.
Action
Text in display
Comments
"
Access
"
Log on to FT128 as
shown in page 35.
Scroll to menu H8.
Maintenance
ACCEPT? H8
"A"
Acknowledge SERVICE signal
ACCEPT? S1
Scroll to menu S6.
Test of alarm devices
ACCEPT? S6
"A"
Test of alarm devices?
ACCEPT?
Press "A" to start the
test.
"A"
Test of alarm devices in progress.
End test? ACCEPT?
The test will now
continue until stopped
via this menu (S6) or
automatically after one
hour or if a fire alarm is
activated.
Press "A" to stop the
test.
"A"
Test of alarm devices?
ACCEPT?
"Return"
Test of alarm devices
ACCEPT? S6
Scroll or press "Return"
to return to menu H8.
"Return"
Maintenance
ACCEPT? H8
Scroll or press "Return"
70
Including Addressable siren 3377 / 4477, Addressable sounder base 3379, wireless detector 4611, and all visual alarm devices
4480, 4481, 4482, 4487.
71
The output activation will be steady (continuous). For the alarm devices 3377 / 4477 and 3379, 4611, 4480, 4481, 4482 and
4487, the tone with the highest priority level (and type "alarm device") will be automatically selected.
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...