Operation Manual
FT128 Rev 2.4
129
27.7
Safe Shut Down of Control Unit (H8/S7)
It's not recommended
to do a safe shutdown of FT128 before power down the FDCIE
which means disconnecting it from 230 V AC and battery. Safe shut down will save the
SSW in a Flash memory and also put the CPU at rest. See also chapter" Restart ", page
82.
It's recommended
to do a safe shut down after commissioning the installation and after
calibration of supervised outputs, change of access code etc.
Note: By restart and power down, the Fault TX relay, which is energised in quiescent /
normal state, will de-energise, i.e. the relay contacts will alternate.
The code for the two restart faults will be 00 after Power off / Power on restart and 03 after
a countdown restart.
Note: Before the very first safe shutdown, the Flash ROM is empty. Then every time safe
shut down is performed, the valid data will be saved in the flash ROM, i.e. any old data will
be overwritten. When the FT128 is powered up, the data stored in the Flash ROM will be
used.
WARNING! If safe shut down is not performed just before you power off a control unit, then
by power on, the Flash ROM might be empty which means the default settings will be
used. Or the stored data might be old and not valid.
Action
Text in display
Comments
"
Access
"
Log on to FT128 as
shown in page 35.
Scroll to menu H8.
Maintenance
ACCEPT? H8
"A"
Acknowledge SERVICE signal
ACCEPT? S1
Scroll to menu S7.
Safe shut down of control unit
ACCEPT? S7
"A"
For safe shut down of control unit
press ACCEPT
"A"
Control unit ready for power down. To restart without
power down press ACCEPT.
The SSW is now saved,
the CPU is at rest and
the CU is ready to be
de-energized.
NOTE!
If you change your mind regarding power down,
press "A" to restart the CU (or wait
5 min.
for an aut.
restart).
Power down – up
or
"A"
or
after 5 min.
Normal restart indication,
see page 82
After the restart, there
will be 2 restart faults,
which has to be
acknowledged, see
chapter "Acknowledge
FAULTS (H6)", page
120.
FAULT: Restart code 0x addr 0
Date: mm-dd Time: hh:mm Serviced
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...