Operation Manual
FT128 Rev 2.4
142
•
Another alarm algorithm can be used (e.g. during working hours).
•
Alarm Delay Facility (ADF) for analogue smoke sensor / detector and sounder
bases combination can be used.
•
Alarm verification Facility (AVF) can be used for convention zone inputs.
•
Co-incidence (two units) fire alarm activation can be used.
•
In an installation with addressable detectors / sensors (e.g. FT128), the affected
detectors can be individually disabled (or whole zones) when the work is in
progress. Bear in mind that the smoke spreads, and consideration must be taken
to adjacent detectors/zones. Disablements can be done automatically via a time
channel (built-in or external) or via menu (H2/B1-B3). Automatic re-enabling can
be used. disable card can also be used to manually disable a zone of smoke
detectors.
•
If there are some alarm investigation procedures for the personnel on site, the alert
annunciation function can be used.
•
Pre-warning can be used as an initial warning before a fire alarm is activated.