Operation Manual
FT128 Rev 2.4
46
11 Disable / Re-enable Control Outputs
All control outputs programmed as type:
•
Control (general)
•
Ventilation (Fire ventilation)
•
Extinguishing
•
Interlocking
….can be collectively disabled via menu H2/B4 type by type. This is indicated by the LED
"Disablements" (L8).
They will remain disabled until they re-enabled again via menu H2/B8.
See also sections "Disable all control, ventilation, extinguishing or interlocking outputs
(H2/B4)" page 91 and "Re-enable all control, ventilation, extinguishing or interlocking
outputs (H2/B8)" page 95.
An interlocking output can be activated for an output test, even if it is disabled.