Operation Manual
FT128 Rev 2.4
47
12 “Disable” Button
When the push button "
Disable
" (P5) is pressed whilst there is an active alarm, all outputs
configured for either the device(s) or zone(s) in alarm, will be disabled. This is indicated by
the disablement LED L8.
The “
Disable
” push button (P5) is provided in the fire brigade section on the front display
to enable the fire brigade personnel to disable (isolate) an active alarm such as a zone of
addressable sensors, conventional zone or individual addressable device.
A single operation of the “
Disable
” button (P5) whilst there is an active alarm will initiate
the following:
•
Disablement of all zones in alarm and/or addressable devices in alarm.
•
Illuminate the “General Disablement” LED L10.
•
Disablement of all the outputs configured for zone(s) or device(s) in alarm.
The output indicators activated as a result of an alarm will not clear automatically after
disablement. A subsequent reset operation is required to restore the FDCIE to the normal
condition.
Note: The “Disable” button will not function unless the “Silence Alarm Devices” button
has been activated first as required by AS4428.3:2010
33
This function is not required in NZ convention.
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...