Operation Manual
FT128 Rev 2.4
71
FAULT: Wrong type of unit zz-aa
Press
to
to see the technical address.
FAULT: Wrong type of unit t.addr xxx
zz-aa
= Zone address,
xxx
= COM loop address
The unit is not the same type as programmed in the SSD. Change the
programming (via EBLWin)
or
the unit.
FAULT: Zone line input zz-aa
Press
to
see the technical address or
the expansion board (4580) number and input number.
FAULT: Zone line input t.addr xxx
zz-aa
= Zone address,
xxx
= COM loop address
Valid for the Multipurpose I/O unit 3361/4461, connected on the COM loop,
monitored Zone Line Input Z: Open circuit in the zone line or wrong / no End-Of-
Line capacitor / short-circuit (if not programmed for fire alarm at short-circuit).
FAULT: Zone line input x exp board x
Valid for the 8 zones exp. board 4580 zone line input x (xxx-xx = zone – address).
The board is mounted in the control unit. Break on the zone line, wrong / no end-
of-line device / short-circuit (if not programmed for fire alarm at short-circuit).
(User programmable fault text; External fault)
Programmable input is connected to any external equipment's fault output. User
definable fault message (< 40 characters) has to be programmed via EBLWin.
16.2
Fault Acknowledge
When a fault is generated in FT128, the following may occur:
•
The LEDs "Fault TX activated" (L11) and "General fault" (L7) are turned ON.
•
LEDs Fault / Disablements “Alarm devices" (L13), "System fault" (L14) and/or "Fire
Brigade TX" (L15) might be turned ON as well.
•
Output for routing equipment (Fault TX) is activated.
•
Output for general fault is activated.
•
Output for general charge fault might be activated.
•
A fault message, date and time, is shown in the FT128 display.
Next to the time might be shown "
More faults
" = more than one fault is generated.
Next to the
time
might be shown "
Serviced
" = the fault is already serviced / corrected.
"
Serviced
" will not be shown if the faults are set to be "Not latched".
Any already Acknowledged fault in the list is indicated by "
/Acknowledged
".
To acknowledge faults in FT128 conduct the following:
•
Login, according to chapter "Access Levels", page 35 .
•
Use
menu H6
(access code for Building officer or Service personnel is required)
for fault acknowledge, see chapter "FAULT Acknowledge (H6) ", page 120.
Menu H6 is a list showing a maximum of 200 faults (not acknowledged faults
and/or acknowledged but not corrected faults). The first fault in the list is the most recent
fault. When a fault is acknowledged and corrected, it will be removed from the list (and a
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...