Operation Manual
FT128 Rev 2.4
77
USB. Right click on it and choose properties. Then click on the Driver Tab. Click
on Update Drivers and choose “Browse my computer for driver software” and
locate the folder for 2.10.00 WHQL (Win7_Win8_Win8.1).
5. Install from folder EBLWin V2.4.4 file named EBLWin.msi.
Win7
: Right click on setup.exe and choose “Run as Administrator”
Win10
: Right click on EBLWin.msi and choose properties then go into the
Compatibility tab. Set as shown in
Error! Reference source not found.
below.
6. Plug in EBLWin key 5094 into another available USB port.
7. Go to Device Manager again and check that your computer has detected EBL*
as a device and assigned it a COM port. Note this COM port number.
8. Launch EBLWin, go to Tools > Log on control unit, the COM port number in step
7 should be displayed.
18.2
Download SSD
Note: An EBLWin USB key (5094) must be used to communicate with the control panel
and download the SSD using EBLWin
≥
V2.x.x.
The PC program
EBLWin
is used for creating the Site Specific Data (SSD) and to
download it into the FT128 Control Unit, Web-server and/or display units 1728, 1736 units.
The SSD will be saved in a file named
xxxxx.EBLWin
(xxxxx is the project name).
The EBLWin key (5094) is a USB device required to log on to the Control Unit, it has a
unique number. The EBLWin key identification number will be registered in the control
panel event log with the date and time stamp for every SSD download performed in the
control panel.
When the installation is ready, i.e. all units connected and the power is turned on, the SSD
download can take place.
Version Control for SSD Download
In EBLWin, when the Download SSD window is opened, the EBLWin checks that the SSD
file originates from the SSD in the control unit. The check will start automatically when the
download SSD window is opened. It is not possible to start SSD download until the check
is completed (or timeout occurs).
If the check shows that the SSD doesn't match the SSD in the control unit, there will be a
dialog window, asking if the download shall proceed anyway.
Note: No password / access code is required to log on to the Control Unit, instead an
EBLWin 5094 key is required.
SSD Download Procedures:
1. Connect the PC to the RS232 port "J3" in the FT128.
2. Start EBLWin and open the required project.
3. Log on to the control unit via the PC (EBLWin).
4. In EBLWin, go to
Tools
menu /
Download
SSD
… Select the control unit as well
as the Display Units (if fitted) or the web server (if fitted), to which the SSD is to
be downloaded.
5. Click
Start
to start the download. The progress bar will indicate the download
progress as shown below.
6. "Control unit download count" / "Document download count" numbers should
match. This is a check to ensure that no an old configuration is downloaded.
7. Click OK.
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...