Operation Manual
FT128 Rev 2.4
86
After 60 minutes
or
"Return"
"Return"
NOTE:
See chapter "
", page
19 regarding priority order.
(When required:
"Access", "password")
"A"
Zone in test mode:
01 02 03 04 End test: ACCEPT
Press "A" to end the test
mode.
"A"
Test of routing equipment? 0
(1 = Yes, 0 = No) ACCEPT
The LED "Test mode" is
turned OFF.
Testing of routing equipment is not permitted in the Australian and NZ convention.
"1", "A"
Test of routing equipment in progress.
nn seconds left.
"nn" starts at 60 and will
count down to 00.
Monthly test is completed!
ACCEPT
"A"
Perform monthly test
ACCEPT? H1
Scroll or press "Return" to
log off.
Notes:
If an alarm point e.g. an MCP is in alarm state when the test mode is terminated, a fire
alarm will be activated.
When "Fire door closing" function is used, the fire door will be closed when the detectors
controlling the door are tested via the test mode.