Operation Manual
FT128 Rev 2.4
88
21.1
Disable Zone (H2/B1)
When a whole zone is disabled, all alarm points within the zone are disabled.
Alarm points can be individually disabled.
Disabled zones can be automatically re-enabled or re-enabled via menu H2/B5.
Action
Text in display
Comments
"Access"
Log on to FT128 as shown
in page 35.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
"A"
Disable zone: 0 0
ACCEPT?
Write zone number
e.g. 01
Disable zone: 01
ACCEPT?
Press "A" to accept.
"A"
Automatic re-enabling: 0 (0=No, 1=Yes)
Time: HH:MM ACCEPT?
Press "1" for auto re-
enabling and accept or
change the time (max. 24
hours). Press "A" to accept.
LED "Disablements" (L8)
will light up.
(Default is current time + 3 hours)
"A"
Zone 01 is disabled
"A"
Disable zone: 0 0
ACCEPT?
If more disablements
required, continue as above
otherwise, press "Return" to
menu B1.
“Return”
Disable zone
ACCEPT? B1
Scroll or press “Return” to
menu H2
“Return”
Disable or re-enable
ACCEPT? H2
Scroll or press “Return”
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...