Operation Manual
FT128 Rev 2.4
13
3 Fire Detection Control & Indicating Equipment
(FDCIE)
3.1
FT128 Specifications
Table 2 FT128 specifications
Item
Specifications
Mains Voltage
230V
AC
(176-264), 1.6A
System Voltage
24
V
DC
@ 1.6A
Current Consumption
Quiescent / alarm current is dependent on other
equipment fitted in FT128, type and number of
expansion boards, connected external equipment, etc.
Ambient Temperature (
⁰
C)
Operating 0 to + 40, Storage -40 to +70
Ambient humidity (%RH)
Maximum 90, non-condensing
Size (mm)
Standard
Small cabinet 630H x 450W x 210D (with door closed)
Large cabinet 920H x 450W x 210D (with door closed)
19” Rack
Small cabinet 678H x 600W x 250D
Large cabinet 1078H x 600W x 250D
Enclosure Material
1.5 Zinc anneal steel
Enclosure Colour
Oyster, powder coated, ripple finish
Approvals
AS7240.2, AS7240.4, AS4428.3 and NZS4512
Standard Inputs / Outputs
Single COM loop, can connect up to 255 devices
Single programmable input I
0
Two programmable Supervised voltage outputs, 0.75
Amp each
One programmable relay outputs, contact rating 2 Amp
One programmable clean contact (N/O or N/C) inputs
One non-programmable relay outputs for ASE (fault)
Two x 24V outputs for Web server, ASE, remote display
units, external applications, etc.
Expansion Boards
Max. 4 of 4580, 4581 or 4583 or any combination
I/O Matrix 4582 board
Max. 8 if no expansion boards fitted.
1
Refer to the technical manual and the current calculation spread sheet.
2
A combination of large and medium enclosures can be used to fit more options.
3
Will be available end of second quarter 2018
4
Refer to FT128 block wiring diagram, drawing no. F665
5
Voltage output V0 is used to provide 2 additional sets of relay contacts on the external termination board SUB835.
6
Expansion boards are internally connected to the COM loop.
7
It is allowed to have up to 4 boards of any type with warning for 4583 if more than 2 are added. Available only in V2.1.0 and
higher.
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...