Operation Manual
FT128 Rev 2.4
50
P r e - w a r n i n g d e t e c t o r 1 2 - 4 5
( u s e r d e f i n a b l e t e x t m e s s a g e )
Example; pre-warning zone 12:
P r e - w a r n i n g z o n e 1 2
( u s e r d e f i n a b l e t e x t m e s s a g e )
LEDs "Alarms queued" (L2) blinking are indicating more than one pre-warning and they
will be automatically scrolled (each 5th second). Pre-warning is automatically reset see
chapter "Alarm reset", page 58.
14.2
Fire Alarm
256 alarms (points or zones) can be presented in the FT128 display.
The following occurs in case of a fire alarm:
•
The buzzer sounds 0.4 sec. each 0.8
th
sec. (0.4 / 0.4 sec.).
•
LEDs "Fire" (L1) are blinking (0.4 / 0.4 sec.).
•
Output for routing equipment (Fire Brigade TX) and outputs type “Routing
equipment” are activated. See also
Note
below.
•
Programmable outputs for fire alarm are activated
•
In the FT128 display, a presentation number (zone/address) with a user
definable text message (alarm text) is shown (if programmed).
Note: Normally the FDCIE relay output "R0" is used as the output for Routing equipment
(Fire Brigade TX). The output will then be activated for fire alarm from any alarm point or
Zone Line Input.
If the fire alarm routing equipment has provision for transmission of several fire alarm
signals and the alarm receiver has provision for reception of several fire alarm signals, the
alarm receiver can take different actions depending on if it is a fire alarm type A or B.
If a
fire alarm type B
is received, it will indicate that only
one
Analogue addressable
smoke, heat or multi detector is activated, which could be a nuisance alarm.
If a
fire alarm type A
is received, it is probably a real fire since fire alarm is then activated
from:
•
Two or more
Analogue addressable smoke, heat or multi detectors.
•
Any
Manual Call Point
•
Any
Zone Line Input
•
Any
programmable input with the trigger condition "General Fire"
For more information on alarm type A and B, see Technical / Programming manual.
Some Fire alarm examples:
One alarm point activating fire alarm
(e.g. detector 12-45)
0 0 1 Z O N E - A D D R 1 2 - 4 5 L A S T Z O N E 1 2 N o . 0 1
" A l a r m t e x t f o r 1 2 - 4 5 "
One zone activating fire alarm
(e.g. zone
14
; a conventional Zone Line Input)
0 0 1 Z O N E 1 4 L A S T Z O N E 1 4 N o . 0 1
" A l a r m t e x t f o r z o n e 1 4 "
More than one alarm point activating fire alarm
(e.g. detectors 12-45 & -46)
39
Programmable outputs for "General fire alarm" and for the activated fire alarm(s).
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...