Operation Manual
FT128 Rev 2.4
52
b) Press “
A
”
c) Navigate similar to the normal menu
"A", "
", "
", "
", "
" and "Return" can be used same as per the normal menu tree, see
chapter "Access Levels", page 35 . The original presentation (the alarm text) will be
automatically displayed again approx. 20 seconds after the push buttons "A", "
", "
",
"
", "
" or "Return" are no longer used.
Available Fire Alarm Menus
•
Display alarms (X1)
One alarm is an alarm point (ZZ-AA) or a zone (ZZ).
•
Display faults (X2
)
Only the fault message for the fault respectively, will be displayed here, not date,
time and "status" information.
•
Display disablements (X3)
Notes Also zones in "Test mode" will be displayed via this menu.
After all disablements, the zones in "Test mode" will be displayed.
•
Disable zone (X4)
Write a zone number (01 – 99) and press A. If more zones are to be disabled,
repeat the procedure.
•
Disable zone / address (X5)
This function is useful e.g. for a manual call point not to continue to generate
alarms because of a broken glass. Write a zone-address and press A. If more
zone-addresses are to be disabled, repeat the procedure.
•
Re-enable zone (X6)
This is a list of disabled zones. Scroll to or write the wanted zone number and
press A. If more zones are to be re-enabled, repeat the procedure.
•
Re-enable zone / address (X7)
This is a list of disabled zone-addresses. Scroll to or write the wanted zone-
address and press "A". If more zone-addresses are to be re-enabled, repeat the
procedure.
•
Disable / Re-enable control (X8)
To disable, press 0 and A. (To re-enable, press 1 and A.).
For more information, see section 21.4 “Disable All Control, Ventilation,
Extinguishing or Interlocking Outputs (H2/B4)” page 91
•
Disable / Re-enable alarm devices (X9)
To disable, press 0 and A. (To re-enable, press 1 and A.).
For more information, see section 21.9 “Disable / Re-Enable Alarm Devices
(H2/B9)” page 96.
14.2.2
Test Mode Alarm
Regarding Test mode, see chapter 20 “Perform Monthly Test (H1)” page 85 and chapter
26 “Perform ZONE TEST (Test Mode) (H7)‘’ page 121.
001 ZONE-ADDR 12-45
ZONE-ADDR: 12-45
LAST ZONE 12
No. 01
001 of 003
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...