Frost Prevention Mode

WhisperComfort incorporates built-in frost prevention technology 
to avoid core freeze up. 

• 

Above 32ºF both exhaust and supply are fully functional

• 

From 32ºF to 20ºF the mechanical damper on the supply air 

closes for 30 minutes, then opens 1 hour at the set high/
low mode. The cycle repeats itself to avoid core freeze up. 
(Exhaust only 30 minutes per 90-minute cycle)

• 

Below 20ºF the mechanical damper on the supply air remains 

closed for 1 hour and opens 10 minutes at low mode. After 
10 minutes the cycle will repeat or change if the temperature 
has risen above 20ºF. (Exhaust only 60 minutes per 80-minute 
cycle)

Settings

WhisperComfort has two 2-speed CFM settings

 

High 

Low 

__________________________________________________

Setting 1.

  

20 CFM 

10 CFM

Setting 2.

  

40 CFM 

20 CFM factory preset

The factory setting is 40/20 CFM. To change to optional 20/10 
CFM setting, move the plug connector located in the junction box 
to the 20 CFM side of receptacle. This step must be completed 
prior to installation. 

Switches

WhisperComfort operates in an on/off and high/low mode. When 
the switch is turned off, the unit does not operate. When the switch 
is turned on, the unit will operate at the high or low mode. A duplex 
switch, designed for a single gang box, may be selected for switch 
operation. Switch labels are provided for convenience to attach to 
the selected switches.

32ºF

Open 1 hr.

Close 30 m.

Open 1 hr.

Open 10 m.

40 CFM

20 CFM

Close 1 hr.

Open 10 m.

19ºF

-13ºF

Balanced Ventilation With Spot ERV

WINTER

SUMMER

Outside

Inside

OPERATION

ON

OFF

HI

LO

Switch is not supplied.