If using this method, please follow instructions in previous 
section regarding using bolts and nuts with larger grounding 
holes.  

 

Use a grounding tin plated solid copper lay-in lug rated for 
direct burial and outdoor use. Lug must be used

 

ILSCO 

GBL-4DBT, Burndy CL501TN. 

 

Attach grounding lug to module frame using a stainless steel 
bolt and lock-nut as shown in figure 3.5. 

 

Tighten stainless steel set screw at the torque specified by 
lug manufacturer to secure copper wire. 

 

Recommended torque value in tightening bolt and nut is 2.3 
N.m (20in-lb). 

 

Using a Grounding Clip with self- tapping screw 

 

Use Tyco Electronics 1954381-1 as grounding clip.                                 

 

As shown in figure 3.6, place the grounding clip onto the 
module frame. 

 

Thread the screw into the hole until the head is flush with the 
base and base is flush with the frame, then tighten the screw 
with 1/4 to 1/2 turn. 
Recommended torque value in tightening self tapping screw 
is between 2.3 and 2.8 Nm. 

 

Insert the wire into the wire slot. Press down on both ends of 
the wire. 

 

Manually, or using channel lock pliers, push the slider over 
the base until it covers the base. This will terminate the wire. 

 

For more information, please refer to Instruction sheet issued 
by Tyco Electronics. 

 

Using a Grounding Clip with bolt and nut 

 

Use Tyco Electronics 1954381-2 as grounding clip. 

 

As shown in figure 3.7, place the grounding clip onto the 
module frame. 

 

Thread the hex nut onto the end of the screw, then using a 
3/8-in. wrench, tighten the nut. 
Recommended torque value in tightening bolt and nut is 
between 1.7 and 2.2 Nm. 

 

Insert the wire into the wire slot. Press down on both ends of 
the wire. 

 

Manually, or using channel lock pliers, push the slider over 
the base until it covers the base. This will terminate the wire. 

 

For more information, please refer to Instruction sheet issued 
by Tyco Electronics. 

 
Module Terminations 

A junction box as a terminal enclosure is equipped for electrical 
connections.   
Modules are equipped with MC

TM

 plugs as a terminal enclosure. 

Use these MC

TM

 plugs for electrical connections.   

 

Junction Box and Terminals 

  Modules are equipped with one junction box containing 

terminals for both, positive and negative polarity, and bypass 
diodes. 

  Each terminal is dedicated to one  polarity with the polarity 

symbols engraved onto the body of the junction box (see 
Figure 4) 

  Each terminal is provided with factory installed lead cables 

and a latching connector for series and string connections. 
Always use these connectors and do not detach them from 
cables. 

 

Latching connectors are type IV and made by Multi-Contact. 
Supplied connectors  listed by UL. 

 

In order to comply with NEC 2008, a locking sleeve needs to 
be used with all connectors that are exposed. 

 

The locking sleeve (PV-SSH4) is made by Multi-Contact and 
can only be released with a special tool also made by 
Multicontact (PV-MS). Locking sleeves are not supplied with 
modules and must be purchased separately. 

 

Conduit 

   In applications where wire raceways or conduit are used, 

follow the applicable codes for outdoor installations..  

  Verify that all fittings are properly installed to protect wires 

against damage and prevent moisture intrusion.  

 

DIODES 
Bypass Diodes 

  When modules in series strings are partially shaded, it may 

cause reverse voltage across cells or modules, because the 
current from other cells in the same series is forced to flow 
through the shaded area. This may cause undesirable heating 
to occur.  

 

The use of a diode to bypass the shaded area can minimize 
both heating and array current reduction. 

  Modules are equipped with factory installed bypass diodes. 

The factory-installed diodes provide proper circuit protection 
for the systems within the specified system voltage, so that 
you do not need any other additional bypass diodes.  

  Contact your SANYO Authorized Representative for proper 

diode type, if it is necessary to add or change diodes due to 
system specifications. 

Figure 4  Configuration of 

Junction Box  

P V U ‑ B 5 0 . 2

I P 6 5

6 0 0 V

P V U ‑ B 5 0 . 2

 

 

Cable 

Connector 
MC

 TM 

Plug

 

Option:  
Safety lock clip 

Negative ( - ) 

Positive ( + ) 

Summary of Contents for HIT Power 225A

Page 1: ...age and injury Work only in dry conditions with dry modules and dry tools Do not stand or step on modules Do not puncture cut scratch or damage the backsheet of a module Backsheet damage will void a module s Limited Warranty and may cause fire Never use modules with a damaged back sheet Do not allow children and unauthorized persons near the installation or storage site of modules Completely groun...

Page 2: ... Figure 1 A module should be attached on a mount or support structure rail by corrosive resistant metal clamps The clamps should be made of aluminum alloy or other material that will reasonably protect against the a risk of electrolytic corrosion Recommendation of bolt torque range 16N m to 20N m The module was tested using Unirac clamps with the specifications below if a different clamp is used i...

Page 3: ...nect electrical load to avoid the hazard of electrical shock To avoid the hazard of electric shock and sparks please connect each cable after confirming the polarity of them is correct Cable conduits should be used in locations where the wiring is inaccessible to children or small animals Module Wiring The number of modules that can be wired in series is recommended to be ten 10 or fewer If connec...

Page 4: ...terminal cup washers The cup washers should be stainless steel or a cup washer made of brass may be used only if a large flat washer made of stainless steel is inserted between the module frame and the cup washer Choose the adequate size for the large flat washer between the module frame and the cup washer so that the cup washer doesn t contact the module frame and is fixed stably to the module fr...

Page 5: ...l enclosure is equipped for electrical connections Modules are equipped with MC TM plugs as a terminal enclosure Use these MC TM plugs for electrical connections Junction Box and Terminals Modules are equipped with one junction box containing terminals for both positive and negative polarity and bypass diodes Each terminal is dedicated to one polarity with the polarity symbols engraved onto the bo...

Page 6: ... to inspect the electrical and mechanical connections annually If you need electrical or mechanical inspection or maintenance it is recommended to have a licensed authorized professional carry out the inspection or maintenance to avoid the hazards of electric shock or injury The return of any modules will not be accepted by SANYO unless prior written authorization has been given by SANYO As part o...

Page 7: ...between the cup washer and module frame and the flat washer diameter must be greater than the cup washer diameter If using a brass cup washer a flat washer must be inserted between the cup washer and module frame and the flat washer diameter must be greater than the cup washer diameter Cup washer Terminal cup Stainless steel or brass Star washer Stainless steel Flat washer Stainless steel Flat was...

Page 8: ...me Longer side Grounding hole 0 205 diameter 5 2mm Flat washer Stainless steel Thickness not less than 0 037 0 94 mm Diameter not less than 0 75 19 05 mm Grounding Lug Bolt Stainless steel 8 10 M5 Nut Stainless steel Copper wire Set screw Stainless screw Star washer Stainless steel Length not less than 0 63 16 mm not more than 0 78 20 mm Self tapping screw Stainless steel Copper wire Frame Longer ...

Page 9: ...ith bolt and nut Note Use the larger ground holes illustrated in Figure 3 1 Grounding Clip Assemblies Tyco Electronics 1954381 2 Glass Backsheet Frame Longer side Grounding hole 0 205 diameter 5 2mm Grounding Clip 8 32 Screw Stainless steel Nut Stainless steel Copper wire Length not less than 0 63 16 mm not more than 0 78 20 mm Copper wire Frame Longer side Glass Backsheet Grounding hole 0 165 dia...

Page 10: ...oc 600 600 600 600 Factory Installed Bypass Diodes 3 3 3 3 Maximum series fuse A 15 15 15 15 Mechanical Specifications Length mm inches Width mm inches Frame Depth mm inches Weight kg pounds Electrical Specifications 1580 62 2 798 31 4 46 1 8 16 35 3 SPECIFICATIONS PVU B5 0 2 600 V PVU B5 0 2 IP6 5 Figure 2 Dimensions Dimensions All HIT Power A Models VBHNxxxAA01 Label Note A module should be inst...

Reviews: