18
SETTING OF COMPRESSOR DELAY TIME
The delay time of compressor can be changed to reduce the load on the power line and to facilitate the
start-up (reset) of the freezer after power failure.
The example in the table 6 is based on the assumption that the delay time is changed to 4 minutes.
Note:
The delay time is set in 3 minutes at the factory.
Table 6. Changing procedure for delay time (change from 3 minutes to 4 minutes)
Description of operation
Key operated
Indication after operation
1
----
The current chamber temperature is
displayed.
2
Press numerical value shift key for
5 seconds.
The first digit is flashed.
3
Set the figure to F05 with the
numerical value shift key.
When pressed, the figure of settable
digit changes.
4 Press set key.
SET
The current delay time is displayed.
The first digit is flashed.
5
Set the figure to 004 with the
numerical value shift key.
When pressed, the figure of the first
digit changes.
6 Press set key.
SET
The delay time is memorized and
the current chamber temperature is
displayed.
• The setting range of the delay time is 3 minutes to 15 minutes. Chamber temperature may not fall
down if the delay time is set in 5 minutes or more depending on the installation environment.
• The compressor delay time set mode returns to the temperature display mode automatically when 90
seconds has passed without any key operation.