18
[Input abnormality indication]
Controller/Converter function selection
Output status
Controller
Converter
OUT
OUT
Output status
selection when
input abnormal
Contents and
Indication
Direct
action
Reverse action
Direct action
Reverse
action
ON (20mA)
or OUT high
limit value
(*)
Overscale
Measured value
has exceeded
Indication range
high limit value.
"
" flashes.
OFF (4mA)
or OUT low
limit value
OFF(4mA)
or
OUT low
limit value
ON (20mA)
or
OUT high
limit value
OFF (4mA)
or
OUT low
limit value
ON (20mA) or
OUT high
limit value
(*)
Underscale
Measured value
has dropped
below Indication
range low limit
value.
"
" flashes.
OFF (4mA)
or
OUT low
limit value
OFF(4mA) or
OUT low
limit value
OFF(4mA)
or
OUT low
limit value
ON (20mA)
or
OUT high
limit value
[Output status selection when input abnormal] is available only for DC input and DC current output.
For other inputs and outputs except for DC input and DC current output, the output status will be
the same as when OFF is selected during [Output status selection when input abnormal].
(*)
: Outputs a value between OFF (4mA) and ON (20mA) or between OUT low limit value and
OUT high limit value, depending on deviation.
Thermocouple, RTD input
Input
Input range
Indication range
Control range
–199.9 to 400.0
–199.9 to 450.0
–205.0 to 450.0
K
,
T
–199.9 to 750.0
–199.9 to 850.0
–209.0 to 850.0
–199.9 to 850.0
–199.9 to 900.0
–210.0 to 900.0
–200 to 850
–210 to 900
–210 to 900
–199.9 to 999.9
–199.9 to 999.9
–211.0 to 1099.9
Pt100
–300 to 1500
–318 to 1600
–318 to 1600
–199.9 to 500.0
–199.9 to 550.0
–206.0 to 550.0
–200 to 500
–207 to 550
–207 to 550
–199.9 to 900.0
–199.9 to 999.9
–211.0 to 999.9
JPt100
–300 to 900
–312 to 1000
–312 to 1000
Indication range and Control range for thermocouple inputs except above:
Input range low limit value–50
(100 ) to input range high limit value+50
(100 )
DC current, voltage input
Indication range : [Scaling low limit value – Scaling span x 1%] to [Scaling high limit value
+ Scaling span x 10%]
However, if the input value is out of the range –1999 to 9999, the PV
display flashes “
” or “
”.
Control range
: [Scaling low limit value – Scaling span x 1%] to [Scaling high limit value
+ Scaling span x 10%]
DC input disconnection
: When DC input is disconnected, PV display flashes “
” for 4 to
20mA DC and 1 to 5V DC input, and “
” for 0 to 1V DC input.
For 0 to 20mA DC, 0 to 5V DC and 0 to 10V DC input, the PV display
indicates the value corresponding with 0mA or 0V input.
Accessories included
: Instruction manual 1 copy
When Heater burnout alarm option is added: Wire harness 3m, 1 length
[Wire type: Twisted; Terminations: Connector (KT7 side)/Cut end (CT side)]
When Heater burnout alarm option is added:
For rating 5A, 10A, 20A
CT (AKT4815)
1 piece
For rating 50A
CT (AKT4816)
1 piece
Accessories sold separately
: 50
shunt resistor (AKT4811) for DC current input
1 piece
11.2 Optional specifications
Heater burnout alarm (option)
Watches the heater current with CT (Current transformer) and detects the burnout.
This alarm is also activated when indication is overscale and underscale.
(To detect Heater burnout, a CT for 50A can also be used for 5A, 10A and 20A ratings, however, this
is not suitable for small ampere ratings due to a low degree of accuracy. For a 20A rating or less, use
a CT designated for 20A.)