19
[Auto-reset]
• If auto-reset “Perform” is selected and the
key is pressed,
the AT indicator flashes and the unit reverts to the PV/SV display
mode.
• If auto-reset is performed, offset correction immediately starts.
• To prevent key misoperation, other settings cannot be performed for 4
minutes after auto-reset starts.
• After auto-reset is completed, the AT indicator is turned off and the
reset value is automatically set.
OUT1 proportional band setting
10
• Sets OUT1 proportional band.
The control action becomes ON/OFF action when set to 0 or 0.0.
• Setting range: 0 to 1000
(0 to 2000 )
With a decimal point, 0.0 to 999.9
( ), DC input: 0.0 to 100.0%
[Percentage of the scaling span (scaling high limit-scaling low limit)]
OUT2 proportional band setting
1.0 times
• Sets OUT2 proportional band.
OUT2 becomes ON/OFF action when set to 0.0.
• Available only when Heating/Cooling control (option) is added.
• Setting range: 0.0 to 10.0 (multiplying factor to OUT1 proportional
band)
Integral time setting
200 seconds
• Sets the integral time.
Setting the value to 0 disables the function (PD action).
• Setting range: 0 to 1000 seconds
Derivative time setting
50 seconds
• Sets the derivative time.
Setting the value to 0 disables the function (PI action).
• Setting range: 0 to 300 seconds
ARW (Anti-reset windup) setting
50%
• Sets the anti-reset windup.
• Available only for PID action.
• Setting range: 0 to 100%
OUT1 proportional cycle setting
• Sets OUT1 proportional cycle.
Relay contact output: 30sec
Non-contact voltage output: 3sec
Not available for ON/OFF action and DC current output type
•
With the relay contact output type, if the proportional cycle time
is decreased, the frequency of the relay action increases and
the life of the relay contact is shortened.
• Setting range: 1 to 120 seconds
OUT2 proportional cycle setting
• Sets OUT2 proportional cycle.
Relay contact output: 30sec
Non-contact voltage output: 3sec
Not available for ON/OFF action and DC current output type
• Available only when Heating/Cooling control (option) is added.
• Setting range: 1 to 120 seconds