22
Parity selection
Even parity
• Selects the parity.
• Not available if Serial communication (option) is not added or
if
is selected during Communication protocol selection.
• No parity:
,
Even parity:
,
Odd parity:
Stop bit selection
1
• Selects the stop bit.
• Not available if Serial communication (option) is not added or
if
is selected during Communication protocol selection.
• Selecting item:
(1) or
(2)
5.6 Auxiliary function setting mode 2
In the PV/SV display mode, if the
and
keys are pressed for approx. 3
seconds, Auxiliary function setting mode 2 can be selected.
The set value can be increased or decreased by pressing the
or
key.
If the
key is pressed, the set value is registered and the next setting item is
selected.
Character
(PV display)
Name, Function, Setting range
Default value
(SV display)
Input type selection
• The input type can be selected from
K (–200 to
1370 )
thermocouple (10 types), RTD (2 types), DC current (2 types) and
DC voltage (4 types) and the unit
/ .
Input type
Input range
–200 to 1370
:
–320 to 2500
:
K
–199.9 to 400.0
:
–199.9 to 750.0 :
J
–200 to 1000
:
–320 to 1800
:
R
0 to 1760
:
0 to 3200
:
S
0 to 1760
:
0 to 3200
:
B
0 to 1820
:
0 to 3300
:
E
–200 to 800
:
–320 to 1500
:
T
–199.9 to 400.0
:
–199.9 to 750.0 :
N
–200 to 1300
:
–320 to 2300
:
PL-
0 to 1390
:
0 to 2500
:
C(W/Re5-26)
0 to 2315
:
0 to 4200
:
–199.9 to 850.0
:
–199.9 to 999.9 :
Pt100
–200 to 850
:
–300 to 1500
:
–199.9 to 500.0
:
–199.9 to 900.0
:
JPt100
–200 to 500
:
–300 to 900
:
4 to 20mA DC
–1999 to 9999:
0 to 20mA DC
–1999 to 9999:
0 to
1V DC
–1999 to 9999:
0 to 10V DC
–1999 to 9999:
1 to
5V DC
–1999 to 9999:
0 to
5V DC
–1999 to 9999: