23
Scaling high limit setting
9999
• Sets scaling high limit value.
• Available only for the DC input
• Setting range: Scaling low limit value to input range high limit value
(The placement of the decimal point follows the selection)
Scaling low limit setting
–1999
• Sets scaling low limit value.
• Available only for the DC input
• Setting range: Input range low limit value to scaling high limit value
(The placement of the decimal point follows the selection)
Decimal point place selection
No decimal point
• Selects a decimal point place.
• Available only for the DC input
• No decimal point
:
1 digit after decimal point :
2 digits after decimal point :
3 digits after decimal point :
PV filter time constant setting
0.0 seconds
• Sets PV filter time constant.
If the value is set too large, it adversely affects control result due to
the delay of response.
• Setting range: 0.0 to 10.0 seconds
OUT1 high limit setting
100%
• Sets the high limit value of OUT1.
Not available if OUT1 is ON/OFF action
• Setting range: OUT1 low limit value to 105%
Setting higher than 100% is effective to DC current output type.
OUT1 low limit setting
0%
• Sets the low limit value of OUT1.
Not available if OUT1 is ON/OFF action
• Setting range: –5% to OUT1 high limit value
Setting less than 0% is effective to DC current output type.
OUT1 ON/OFF action hysteresis setting
1.0
• Sets ON/OFF action hysteresis for OUT1.
Available only when OUT1 is ON/OFF action
• Setting range: 0.1 to 100.0
( )
For DC input, 1 to 1000 (The placement of the decimal
point follows the selection)
OUT2 action mode selection
Air cooling
• Selects a cooling action from Air cooling, Oil cooling and Water
cooling.
Not available if OUT2 is ON/OFF action or if Heating/Cooling control
(option) is not applied
•
: Air cooling (Linear characteristic)
: Oil cooling (The 1.5th power of the linear characteristic)
: Water cooling (The 2nd power of the linear characteristic)