24
OUT2 high limit setting
100%
• Sets the high limit value of OUT2.
• Not available if OUT2 is ON/OFF action or if Heating/Cooling control
(option) is not applied
• Setting range: OUT2 low limit value to 105%
(Setting higher than 100% is effective to DC current output type.)
OUT2 low limit setting
0%
• Sets the low limit value of OUT2.
• Not available if OUT2 is ON/OFF action or if Heating/Cooling control
(option) is not applied
• Setting range: –5% to OUT2 high limit value
(Setting less than 0% is effective to DC current output type.)
Overlap band/Dead band setting
0.0
• Sets overlap band and dead band value for OUT1 and OUT2.
+ Set value: Dead band
– Set value: Overlap band
• Not available if OUT2 is ON/OFF action or if Heating/Cooling control
(option) is not applied
• Setting range: –100.0 to 100.0
( )
DC input: –1000 to 1000 (The placement of the decimal
point follows the selection)
OUT2 ON/OFF action hysteresis setting
1.0
• Sets ON/OFF action hysteresis for OUT2.
• Available when OUT2 is ON/OFF action or when Heating/Cooling
control (option) is applied
• Setting range: 0.1 to 100.0
( )
For DC input, 1 to 1000 (The placement of the decimal
point follows the selection)
A1 type selection
No alarm action
• Selects A1 type.
• Selecting item
No alarm action
:
High limit alarm
:
Low limit alarm
:
High/Low limits alarm
:
High/Low limit range alarm
:
Process high alarm
:
Process low alarm
:
High limit alarm with standby
:
Low limit alarm with standby
:
High/Low limits alarm with standby: