40
Dielectric strength
Between input terminal and ground terminal,
1.5kV AC for 1 minute
Between input terminal and power terminal,
1.5kV AC for 1 minute
Between output terminal and ground terminal, 1.5kV AC for 1 minute
Between output terminal and power terminal, 1.5kV AC for 1 minute
Between power terminal and ground terminal, 1.5kV AC for 1 minute
Weight
: Approx. 370
g
External dimension
: 96 x 96 x 98.5mm (W x H x D)
Material
: Case, Flame-resistant resin
Color
: Case, Ash gray
Attached function
[Sensor correction function]
[Set value lock function]
[Input abnormality indication]
Output status
OUT1
OUT2
Output
selection
when input
abnormal
Contents and
Indication
Direct action
Reverse
action
Direct action
Reverse
action
ON (20mA) or
OUT1 high
limit value
(*)
ON (20mA) or
OUT2 high
limit value
(*)
Overscale
Measured value
has exceeded
Indication range
high limit value.
"
" flashes.
OFF (4mA) or
OUT1 low
limit value
OFF (4mA) or
OUT1 low
limit value
OFF (4mA) or
OUT2 low
limit value
OFF (4mA) or
OUT2 low
limit value
ON (20mA) or
OUT1 high
limit value
(*)
ON (20mA) or
OUT2 high
limit value
(*)
Underscale
Measured value
has dropped
below Indication
range low limit
value.
"
" flashes.
OFF (4mA) or
OUT1 low
limit value
OFF (4mA) or
OUT1 low
limit value
OFF (4mA) or
OUT2 low
limit value
OFF (4mA) or
OUT2 low
limit value
Only for DC input and DC current output type, [Output status selection when input
abnormal] is available. For other inputs and outputs except for DC input and DC
current output, the output status will be the same one as when OFF is selected
during [Output status selection when input abnormal].
For manual control, the preset manipulated variable (MV) is outputted.
(*)
: Outputs a value between OFF (4mA) and ON (20mA) or between OUT1 (OUT2)
low limit value and OUT1 (OUT2) high limit value, depending on deviation.
Thermocouple, RTD input:
Input
Input range
Indication range
Control range
–199.9 to 400.0
–199.9 to 450.0
–205.0 to 450.0
K
,
T
–199.9 to 750.0
–199.9 to 850.0
–209.0 to 850.0
–199.9 to 850.0
–199.9 to 900.0
–210.0 to 900.0
–200 to 850
–210 to 900
–210 to 900
–199.9 to 999.9
–199.9 to 999.9
–211.0 to 1099.9
Pt100
–300 to 1500
–318 to 1600
–318 to 1600
–199.9 to 500.0
–199.9 to 550.0
–206.0 to 550.0
–200 to 500
–207 to 550
–207 to 550
–199.9 to 900.0
–199.9 to 999.9
–211.0 to 999.9
JPt100
–300 to 900
–312 to 1000
–312 to 1000
For the thermocouple inputs other than the above, both the Indication range and
Control range are: Input range low limit value – 50
(100 ) to Input range high
limit value + 50
(100 )