43
OUT2 ON/OFF action hysteresis:
Thermocouple, RTD input: 0.1 to 100.0
( )
DC current, voltage input: 1 to 1000 (The placement of the decimal
point follows the selection)
Output
Relay contact, 1a
Control capacity, 3A
250V AC (resistive load)
1A
250V AC (inductive load cosø=0.4)
Electrical life, 100,000 cycles
Non-contact voltage output
12
+2
0
V DC
maximum 40mA (short circuit protected)
DC current output, 4 to 20mA DC
Load resistance, maximum 550
OUT2 action mode selection function:
One cooling mode can be selected by keypad operation from the following.
Air cooling (Linear characteristic)
Oil cooling (1.5th power of the linear characteristic)
Water cooling (2nd power of the linear characteristic)
Serial communication
The following operations can be carried out from the external computer.
When this option is added, SV2 setting is not available.
(1)Reading and setting of SV, PID and various set values
(2) Reading of the PV and action status
(3) Change of the functions
Cable length
: Max. communication distance 1000m,
Cable resistance; Within 50
Communication line
: EIA RS-485
Communication method
: Half-duplex communication start stop synchronous
Communication speed
: 2400, 4800, 9600, 19200bps (Selectable by keypad)
Parity
: Even, Odd and No parity (Selectable by keypad)
Stop bit
: 1, 2 (Selectable by keypad)
Communication protocol
: Modbus RTU, Modbus ASCII (Selectable by keypad)
Connectable number of units
: Maximum 31 units to 1 host computer
Communication error detection: Parity, checksum (LRC, CRC)
10. Troubleshooting
If any malfunctions occur, refer to the following items after checking the power of the
controller.
Warning
Turn the power supply to the instrument off before wiring or checking.
Working on or touching the terminal with the power switched on may result in
severe injury or death due to Electric Shock.