Press            during each item is displayed to change the setting value.

Press               to display the confirmation window.  

 Select [YES] and press            to decide the setting value.

However no value is changed, the confirmation window is skipped and 
it displays the measuring value display.

*3 It skips when [30] is set at pulse input 1.

*1 It skips when [Peak] or [30min] is set at
     power demand type.
*2 It skips when except [30min] is set at
     power demand type.

*4 It skips when [Clock] is selected at
     pulse input 1.

*5 It skips when [0] is set at auto-display 

setting.

*6 It skips when [YES] is selected at reset 
     all integral value.

*7 It skips when [OFF]  is selected at 
     the previous program. 

Measuring value display

Enter password

Phase/Wire

Power

 

demand type

Power demand

 interval  *1

Power demand 

interval 2 *1

Power input type *2

Pulse type *2

Pulse rate (elecric power

convertion)      *2

Pulse constant value *2

Current demand interval

Calcuration method

for 30-min demand *2

CT type

Primary side 

current of CT

Rated voltage

VT ratio

Over voltage

Protocol

Device number

Transmission

speed

Transmission

format

Stop bit

Response time

Auto-off

Luminance

Alarm blinking

Update cycle

Auto-display

Display cycle

*5

Temperature

correction

Reset all 

integral value

Calendar

timer

Password

setting

Setting Mode

Under voltage

Over current

Under current

Power

 measurement

Pulse

【Demand】

Communication

Optional function

Time program

Calendar timer

Password

Confirmation Mode

Measuring value display

Setting confirmation

NO

Setting confirmation

YES

10. Setting Flow

11. How to Set the Parameters related to

Power Measurement

Set before measuring.

Phase / Wire

Rated voltage

Conversion rate (P)

Conversion rate (-P)

Calender timer

VT ratio

Over Voltage/ Over Voltage 2

Under Voltage / Under Voltage 2

Over Current /Over Current 2

◆Under

 Current /Under Current 2

CT type

Primary side current of CT

Select measured phase and wire system.

How to Enter Password

How to Initialize Password

It is necessary to enter password to shift to setting
mode. Enter [0000] and shift to password setting 
mode when you set password at the first time.

*When setting password, be careful for handling and note it.

Measuring value display

Measuring value display

Password

entry window

Password

entry window

Password
initialize window

Setting

mode of

power

measurement

When you forget the password, initialize it in the 
following procedures. (Initial: [0000])
It is impossible to decode the set password.

Increase
Shift entered digit to the right

Enter password
from left to right 

If the password is wrong, 
[FAIL] is displayed and it returns
to the password entry window.
*If you make wrong password

5 times, you can’t set 1-hour after.

+

30 sec.

Return to the measuring value display

Initialize[YES]

Not initialize[NO]

To use CT with secondary side current 5A: [5] (initial)
To use CT with secondary side current 1A: [1]

When the system is not matched with the measure system, 

it doesn’t measure correctly

Select using CT type (secondary side current).

Set the primary side current of using CT.
Enter the primary side current of CT that is set at CT type
setting. 

Increase

Decrease

[Set range] 1 to 65535 (initial: 5)

Primary side current of using CT is 400A: [400]

Set the rated voltage of measured voltage.

Select the voltage input method, input voltage directly 
or uses a voltage transformer (VT: secondary side rating
110V) and set VT ratio.

Increase

Decrease

Increase

Decrease

Increase

Decrease

[Set range] 100 to 500 (initial:100)

Increase

Decrease

[Set range] 0.00 to 99.99 /1kWh

(initial:10.00)

Increase

Decrease

[Set range] 0.00 to 99.99 /1kWh

(initial:10.00)

Increase

Decrease

[Set range] 
            Jan. 1st, 2000  00:00: to 
            Dec. 31st, 2099 23:59

[Set range] 1.00 to 600.00 (initial:1.00)

Increase

Decrease

[Set range] 100.0 to 120.0 %  

(initial:105.0)

Increase

Decrease

[Set range] 100.0 to 120.0 %  

(initial:105.0)

Increase

Decrease

[Set range] 0.0 to 100.0 %  

(initial:0.0)

Increase

Decrease

[Set range] 0.0 to 100.0 %  

(initial:0.0)

Increase

Decrease

[Set range] 5.0 to 100.0 %

(initial: 95.0)

[Set range] 5.0 to 100.0 %

(initial: 95.0)

Increase

Decrease

[Set range] 0.1 to 120.0 %  

(initial: 100.0)

Increase

Decrease

[Set range] 0.1 to 120.0 %  

(initial: 100.0)

Set the ratio for the rated voltage to judge to be over voltage
at [over volt] window.

Set the ratio for the rated current to judge to be under current
at [under curr] window.

Press                , and [over volt 2] is displayed. 
At this window, set a ratio of voltage to clear overt voltage.

Press                , and [under curr 2] is displayed. 
At this window, set a ratio of current to clear under current.

Press                , and [under volt 2] is displayed. 
At this window, set a ratio of voltage to clear under voltage.

Press                , and [under curr 2] is displayed. 
At this window, set a ratio of voltage to clear under voltage.

Set the ratio for the rated voltage to judge to be under

voltage at [under volt] window.

Set the ratio for the rated voltage to judge to be over

current at [over curr] window.

Input directly without VT: [1.00]

Use VT

: [1.01 to 600.00]

Set the conversion rate per integral active power 1 kWh.
You can set 5 kinds of rate for each time zone, all-time, 
time zone 1, time zone 2, time zone 3 and time zone 4.
Rate for all-time is used when time program is not set.
When you set one or more time programs, the rates for 
time zone 1, 2, 3 and 4 are used. Rate for all-time is not used. 

Set the conversion rate per integral export power (-P) 1 kWh.

Set the date and time.

In order to use the logging function, set the date and time.

Refer to User’s manual for the other settings.

Time zone

None: all-time

T1: time zone 1    T2: time zone 2
T3: time zone 3    T4: time zone 4

Time zone

None: all-time

T1: time zone 1    T2: time zone 2
T3: time zone 3    T4: time zone 4

Single-phase 2-wire (initial)

Single-phase 3-wire

Three-phase 4-wire

Three-phase 3-wire

Rate(P)

Total, T1-4

Rate(-P)

Total, T1-4

Pulse input 1

Clock 

synchronize *3

Pulse input 2

Prescale 1 *4

Pulse output 1 

Pulse output 2

Prescale 2

*7

Program 7

*7

Program 8

*7

Program 9

*7

Program 10

Program 1

*7

Program 2

*7

Program 3

*7

Program 4

*7

Program 5

*7

Program 6

Select setting item with              and press              

and the value will be blinking. 

 

Set with             and 

When you select [YES] with the confirmation window

and press             , the setting values are decided.

Reset integral

value 1       *6

Version

Reset count

value 1     *6

Reset count

value 2     *6

Reset logging

data           *6

Reset integral

value 2       *6

Reset integral

value 3       *6