Press during each item is displayed to change the setting value.
Press to display the confirmation window.
Select [YES] and press to decide the setting value.
However no value is changed, the confirmation window is skipped and
it displays the measuring value display.
*3 It skips when [30] is set at pulse input 1.
*1 It skips when [Peak] or [30min] is set at
power demand type.
*2 It skips when except [30min] is set at
power demand type.
*4 It skips when [Clock] is selected at
pulse input 1.
*5 It skips when [0] is set at auto-display
setting.
*6 It skips when [YES] is selected at reset
all integral value.
*7 It skips when [OFF] is selected at
the previous program.
Measuring value display
Enter password
Phase/Wire
Power
demand type
Power demand
interval *1
Power demand
interval 2 *1
Power input type *2
Pulse type *2
Pulse rate (elecric power
convertion) *2
Pulse constant value *2
Current demand interval
Calcuration method
for 30-min demand *2
CT type
Primary side
current of CT
Rated voltage
VT ratio
Over voltage
Protocol
Device number
Transmission
speed
Transmission
format
Stop bit
Response time
Auto-off
Luminance
Alarm blinking
Update cycle
Auto-display
Display cycle
*5
Temperature
correction
Reset all
integral value
Calendar
timer
Password
setting
Setting Mode
Under voltage
Over current
Under current
【
Power
measurement
】
【
Pulse
】
【Demand】
【
Communication
】
【
Optional function
】
【
Time program
】
【
Calendar timer
】
【
Password
】
Confirmation Mode
Measuring value display
Setting confirmation
NO
Setting confirmation
YES
10. Setting Flow
11. How to Set the Parameters related to
Power Measurement
Set before measuring.
◆
Phase / Wire
◆
Rated voltage
◆
Conversion rate (P)
◆
Conversion rate (-P)
◆
Calender timer
◆
VT ratio
◆
Over Voltage/ Over Voltage 2
◆
Under Voltage / Under Voltage 2
◆
Over Current /Over Current 2
◆Under
Current /Under Current 2
◆
CT type
◆
Primary side current of CT
Select measured phase and wire system.
◆
How to Enter Password
◆
How to Initialize Password
It is necessary to enter password to shift to setting
mode. Enter [0000] and shift to password setting
mode when you set password at the first time.
*When setting password, be careful for handling and note it.
Measuring value display
Measuring value display
Password
entry window
Password
entry window
Password
initialize window
Setting
mode of
power
measurement
When you forget the password, initialize it in the
following procedures. (Initial: [0000])
It is impossible to decode the set password.
Increase
Shift entered digit to the right
Enter password
from left to right
If the password is wrong,
[FAIL] is displayed and it returns
to the password entry window.
*If you make wrong password
5 times, you can’t set 1-hour after.
+
30 sec.
Return to the measuring value display
Initialize[YES]
Not initialize[NO]
To use CT with secondary side current 5A: [5] (initial)
To use CT with secondary side current 1A: [1]
When the system is not matched with the measure system,
it doesn’t measure correctly
Select using CT type (secondary side current).
Set the primary side current of using CT.
Enter the primary side current of CT that is set at CT type
setting.
Increase
Decrease
[Set range] 1 to 65535 (initial: 5)
Primary side current of using CT is 400A: [400]
Set the rated voltage of measured voltage.
Select the voltage input method, input voltage directly
or uses a voltage transformer (VT: secondary side rating
110V) and set VT ratio.
Increase
Decrease
Increase
Decrease
Increase
Decrease
[Set range] 100 to 500 (initial:100)
Increase
Decrease
[Set range] 0.00 to 99.99 /1kWh
(initial:10.00)
Increase
Decrease
[Set range] 0.00 to 99.99 /1kWh
(initial:10.00)
Increase
Decrease
[Set range]
Jan. 1st, 2000 00:00: to
Dec. 31st, 2099 23:59
[Set range] 1.00 to 600.00 (initial:1.00)
Increase
Decrease
[Set range] 100.0 to 120.0 %
(initial:105.0)
Increase
Decrease
[Set range] 100.0 to 120.0 %
(initial:105.0)
Increase
Decrease
[Set range] 0.0 to 100.0 %
(initial:0.0)
Increase
Decrease
[Set range] 0.0 to 100.0 %
(initial:0.0)
Increase
Decrease
[Set range] 5.0 to 100.0 %
(initial: 95.0)
[Set range] 5.0 to 100.0 %
(initial: 95.0)
Increase
Decrease
[Set range] 0.1 to 120.0 %
(initial: 100.0)
Increase
Decrease
[Set range] 0.1 to 120.0 %
(initial: 100.0)
Set the ratio for the rated voltage to judge to be over voltage
at [over volt] window.
Set the ratio for the rated current to judge to be under current
at [under curr] window.
Press , and [over volt 2] is displayed.
At this window, set a ratio of voltage to clear overt voltage.
Press , and [under curr 2] is displayed.
At this window, set a ratio of current to clear under current.
Press , and [under volt 2] is displayed.
At this window, set a ratio of voltage to clear under voltage.
Press , and [under curr 2] is displayed.
At this window, set a ratio of voltage to clear under voltage.
Set the ratio for the rated voltage to judge to be under
voltage at [under volt] window.
Set the ratio for the rated voltage to judge to be over
current at [over curr] window.
Input directly without VT: [1.00]
Use VT
: [1.01 to 600.00]
Set the conversion rate per integral active power 1 kWh.
You can set 5 kinds of rate for each time zone, all-time,
time zone 1, time zone 2, time zone 3 and time zone 4.
Rate for all-time is used when time program is not set.
When you set one or more time programs, the rates for
time zone 1, 2, 3 and 4 are used. Rate for all-time is not used.
Set the conversion rate per integral export power (-P) 1 kWh.
Set the date and time.
In order to use the logging function, set the date and time.
・
Refer to User’s manual for the other settings.
Time zone
None: all-time
T1: time zone 1 T2: time zone 2
T3: time zone 3 T4: time zone 4
Time zone
None: all-time
T1: time zone 1 T2: time zone 2
T3: time zone 3 T4: time zone 4
Single-phase 2-wire (initial)
Single-phase 3-wire
Three-phase 4-wire
Three-phase 3-wire
Rate(P)
Total, T1-4
Rate(-P)
Total, T1-4
Pulse input 1
Clock
synchronize *3
Pulse input 2
Prescale 1 *4
Pulse output 1
Pulse output 2
Prescale 2
*7
Program 7
*7
Program 8
*7
Program 9
*7
Program 10
Program 1
*7
Program 2
*7
Program 3
*7
Program 4
*7
Program 5
*7
Program 6
Select setting item with and press
and the value will be blinking.
Set with and
When you select [YES] with the confirmation window
and press , the setting values are decided.
Reset integral
value 1 *6
Version
Reset count
value 1 *6
Reset count
value 2 *6
Reset logging
data *6
Reset integral
value 2 *6
Reset integral
value 3 *6