LT4H-W

Setting the operation mode and time range

Setting procedure 1)  Setting the time range (Timer T

1

/Timer T

2

)

Set the time range with the DIP switches on the side of the LT4H-W timer.

Setting procedure 2)  Setting the operation mode

Set the operation mode with the keys on the front of the LT4H-W timer.

Front display section

DIP switch

Item

DIP switch No.

1

2

3

ON

ON

ON

0.01 s to 99.99 s

OFF

OFF

OFF

0.1 s to 999.9 s

ON

OFF

OFF

1 s to 9999 s

OFF

ON

OFF

0 min 01 s to 99 min 59 s

ON

ON

OFF

0.1 min to 999.9 min

OFF

OFF

ON

0 h 01 min to 99 h 59 min

ON

OFF

ON

0.1 h to 999.9 h

OFF

ON

ON

1 h to 9999 h

Table 1: Setting the time range (Timer T

1

)

Table 2: Setting the time range (Timer T

2

)

Time range

Time range

(Timer T

1

)

Refer to table 1

1

2

3

Minimum input reset, start, and

stop signal width

20 ms

1 ms

*4

Time delay direction

Addition Subtraction

5

Time range

(Timer T

2

)

Refer to table 2

6

7

8

ON

OFF

DIP switch No.

6

7

8

ON

ON

ON

OFF

OFF

OFF

ON

OFF

OFF

OFF

ON

OFF

ON

ON

OFF

OFF

OFF

ON

ON

OFF

ON

OFF

ON

ON

Time range

Notes: 1) Set the DIP switches before installing the timer.

2) When the DIP SW setting is changed, turn off the power once.
3) The DIP switches are set as ON before shipping.

* The 8-pin type does not have the stop input, so that the dip

switch can be changed over between reset and start inputs.
The signal range of the lock input is fixed (minimum 20 ms).

1

2

3

DIP switches

4

5

6

7

8

ON

Q

Elapsed time display

W

Set time display

E

T

1

/T

2

operation indicator

R

T

1

/T

2

setting value 

selectable indicator

T

Controlled output 
indicator

Y

Lock indicator

U

Time units display

I

UP keys
Changes the corresponding digit of the set time in the addition direc-
tion (upwards)

O

DOWN keys
Changes the corresponding digit of the set time in the subtraction
direction (downwards)

P

RESET switch
Resets the elapsed time and the output

{

SET/LOCK switch
Changes over the display between T

1

/T

2

settings, sets the operation

mode, checks the operation mode and locks the operation of each key
(such as up, down or reset key).

T2

T1

T2

DOWN

T1

UP

SET/LOCK

RESET

s

m

h

LOCK

OP.

LT4H-W

TIMER

11

10

6

5

4

9

8

7

2

1

3

Fourth digit

First digit

1) Setting or changing the operation mode

(1) When the UP or DOWN key at the first digit is pressed with the SET/LOCK
switch pressed, the mode is changed over to the setting mode.
(2) Now release the SET/LOCK switch.
(3) The operation mode in the setting mode is changed over sequentially in the left or right direction by pressing the UP or DOWN key at the first digit, respectively.

(4) The operational mode displayed at present is set by pressing the RESET switch, and the display returns to the normal condition.

2) Setting (changing) the time

(1) Pressing the SET/LOCK key switches the set value display between T1 and T2. Display the timer (T1 or T2) which is to be set (or changed).
(2) After displaying the timer (T1 or T2) which is to be set, press the UP or DOWN key to change the time.

• Checking the operation mode

When the UP or DOWN key at the second digit is pressed with the SET/LOCK switch pressed, the operational mode can be checked.
The display returns to the normal condition after indicating the operational mode for about two seconds. (While the display indicates the operational mode for about two
seconds, the other indicators continue to operate normally.)

• Setting the lock

When the UP or DOWN key at the fourth digit is pressed with the SET/LOCK switch pressed, all keys on the unit are locked.
The timer does not accept any of UP, DOWN and RESET keys.
To release the lock setting, press the UP or DOWN key at the fourth digit again with the set/lock switch pressed.
* Operational mode, adding and subtracting and minimum input signal range cannot be set at T

1

and T

2

, respectively.

• Changing over the T

1

/T

2

setting display

The T1/T2 setting display is changed over by pressing the SET/LOCK switch. (This operation gives no effect on the other operations. The set time and elapsed time
(residual time) at T

1

are linked with those at T

2

.)

• Changing the set time

1) It is possible to change the set time with the UP and DOWN keys even during time delay with the timer. However, be aware of the following points.

(1) If the set time is changed to less than the elapsed time with the time delay set to the addition direction, time delay will continue until the elapsed time reaches full

scale, returns to zero, and then reaches the new set time. If the set time is changed to a time above the elapsed time, the time delay will continue until the elapsed
time reaches the new set time.

(2) If the time delay is set to the subtraction direction, time delay will continue until “0” regardless of the new set time.

2) When the set times at T

1

and T

2

are set to 0, the output becomes ON only while the start input is carried out. However, while the reset input is carried out, the output

becomes OFF.

Ex: Setting operation mode display
(PULSE-A example)

Pulse input
OFF-start
Repeating operation

Pulse input
OFF-start
One operation

Pulse input
ON-start
Repeating operation

Integrating input
OFF-start
One operation

Integrating input
ON-start
Repeating operation

OFF-start
Repeating operation

Integrating input

0.01 s to 99.99 s

0.1 s to 999.9 s

1 s to 9999 s

0 min 01 s to 99 min 59 s

0.1 min to 999.9 min

0 h 01 min to 99 h 59 min

0.1 h to 999.9 h

1 h to 9999 h

(same for screw terminal type and 8-pin type.)

All Rights Reserved © C

OPYRIGHT

 Matsushita Electric Works, Ltd.

Summary of Contents for LT4H/-L

Page 1: ...Output Operating voltage Power down insurance Terminal type Part number 9 999 s 0 001 s 99 99 s 0 01 s 999 9 s 0 1 s 9999 s 1 s 99 min 59 s 1 s 999 9 min 0 1 min 99 h 59 min 1 min 999 9 h 0 1 h Power ON delay 1 Power ON delay 2 Signal ON delay Signal OFF delay Pulse One shot Pulse ON delay Signal Flicker Totalizing ON delay 8 modes Relay 1 c Transistor 1 a 100 to 240 V AC 24 V AC 100 to 240 V AC 2...

Page 2: ...Shortened body 70 1 mm 2 760 inch underhead 4 Compliant with UL c UL and CE 48 1 890 48 1 890 64 5 2 539 UL File No E122222 C UL File No E122222 LT4H L Timers mm inch Product types Time range Product name Operating mode Output Operating voltage Power down insurance Terminal type Part number 9 999 s 0 001 s 99 99 s 0 01 s 999 9 s 0 1 s 9999 s 1 s 99 min 59 s 1 s 999 9 min 0 1 min 99 h 59 min 1 min ...

Page 3: ... AC DC 50 60 Hz common Max 10 V A 100 mA 30 V DC 12 to 24 V DC Max 3 W DC type Transistor output type AC type AC DC type DC type Rating Time accuracy max Contact Life Electrical Mechanical Operating conditions Rated operating voltage Rated frequency Rated power consumption Rated control capacity Time range Time counting direction Operation mode Start Reset Stop input Lock input Input signal Indica...

Page 4: ...gasket ATC18002 supplied Panel 63 5 2 500 48 1 890 66 2 598 50 1 969 48 1 890 LT4H TIMER UP OP RST LOCK DOWN LOCK RESET s m h Mounting frame for flush mount AT8 DA4 supplied Panel Rubber gasket ATC18002 supplied 1 039 11 pin type 11p cap AT8 DP11 sold separately 8 pin type 8p cap AD8 RC sold separately 48 1 890 90 3 543 48 1 890 66 2 598 50 1 969 DIN rail terminal block 8 pin type AT8 DF8K sold se...

Page 5: ... OP TIMER LT4H Changing the set time 1 It is possible to change the set time with the up and down keys even dur ing time delay with the timer However be aware of the following points 1 If the set time is changed to less than the elapsed time with the time delay set to the addition direction time delay will continue until the elapsed time reaches full scale returns to zero and then reaches the new ...

Page 6: ...ddition or stops at 0 sub traction Ignores start input Stops delay time operation at stop ON Restarts delay time operation at stop OFF 1 2 3 OFF OFF OFF Set the operation mode section of the DIP switches no s 1 2 and 3 on the side of the timer as shown Clears elapsed time value at power ON Time delay starts at start ON and elapsed time value or output resets at start OFF Instantaneous time delay s...

Page 7: ...Stops delay time operation at stop ON Restarts delay time operation at stop OFF In order to have the time delay start at power ON or reset at power OFF short out the start input beforehand 1 2 3 OFF OFF ON Set the operation mode section of the DIP switches no s 1 2 and 3 on the side of the timer as shown Clears elapsed time value at power ON Time delay starts at start ON Ignores start input during...

Page 8: ...and CE 9 Low Price All this at an affordable price to provide you with unmatched cost performance 48 1 890 48 1 890 64 5 2 539 8 pin type 11 pin type Screw terminal type Time range Operating mode Output Operating voltage Power down insurance Terminal type Part number 99 99s 999 9s 9999s 99min59s 999 9min 99h59min 999 9h 9999h Pulse input Delayed one shot OFF start flicker ON start flicker Integrat...

Page 9: ...med out 1 Form A Open collector Min 107 ope At rated control voltage 12 to 24 V DC Max 3 W 100 to 240V AC 24V AC 50 60 Hz common Max 10 V A 100 mA 30 V DC 12 to 24 V DC Max 3 W DC type Transistor output type AC type DC type Rating Time accuracy max Contact Life Electrical Mechanical Operating conditions Rated operating voltage Rated frequency Rated power consumption Rated control capacity Time ran...

Page 10: ...for flush mount for flush mount Mounting frame dimension is for 8 pin type 90 0 95 5 3 543 3 760 AT8 DLA1 sold separately Device installation rail 11 pin type AT8 DF11K sold separately DIN rail terminal block 8 pin type AT8 DF8K sold separately 80min 3 150min 80min 3 150min 45 0 0 6 1 772 0 024 45 0 0 6 1 772 0 024 45 0 0 6 1 772 0 024 A 48 n 2 5 0 6 0 A 1 890 n 098 024 0 A When n timers are conti...

Page 11: ... N C 3 5 4 2 1 11 10 9 8 7 6 Reset Start Stop Lock 3 5 4 2 1 11 10 9 8 7 6 Operating voltage Reset Start Stop Lock Relay output type Transistor output type Screw terminal type 5 4 3 2 1 10 9 8 7 6 N O N C Operating voltage Reset Start Stop Lock 5 4 3 2 1 10 9 8 7 6 Reset Start Stop Lock Operating voltage Note For connecting the output leads of the transistor output type refer to 5 Transistor outpu...

Page 12: ...h and the display returns to the normal condition 2 Setting changing the time 1 Pressing the SET LOCK key switches the set value display between T1 and T2 Display the timer T1 or T2 which is to be set or changed 2 After displaying the timer T1 or T2 which is to be set press the UP or DOWN key to change the time Checking the operation mode When the UP or DOWN key at the second digit is pressed with...

Page 13: ...put ta Power T1 tc td T2 te tc td tf tg T2 T1 th t1 ta tb T1 t2 tg th T2 te tf T1 supply ON start flicker C Remarks and notes ON start repeating operation t1 T1 t2 T2 C PULSE Start Reset Stop Output Power supply ta tb T1 tc td T2 ta tb tc td t1 t2 T1 T1 T2 T1 T2 ON start repeating operation t1 T1 t2 T2 C INTEGRATION tb Stop Start Reset Output Power ta tc td T2 T1 tf tg tc td te t1 th T1 T2 ta tb T...

Page 14: ...r opera tions use contacts with as short a bounce time as possible Also select a minimum input signal width of 20 ms 2 Non contact point input Connect with an open collector Use transistors whose characteristics satisfy the criteria given below VCEO 20 V min IC 20 mA min ICBO 6µA max Also use transistors with a residual volt age of less than 2 V when the transistor is on 8 pin type Screw terminal ...

Page 15: ... load of the controlled output make sure that it is lower than the rated control capacity 4 Operation of LT4H digital timer 1 Turning on and off the power supply while operating in A2 Power on delay 2 or G Totalizing On delay will result in a timer error to be generated due to the characteristics of the internal circuitry Therefore use the start input or stop input Not related to the start input 2...

Page 16: ...2 2 This timer employs a power supply without a transformer so the power and input signal terminals are not insulated 1 When a sensor is connected to the input circuit install double insulation on the sensor side 2 In the case of contact input use dual insulated relays etc 3 The load connected to the output con tact should have basic insulation This timer is protected with basic insula tion and ca...

Reviews: