10.
Model
(1)
Model code
1: MDF-DU502VH
2: MDF-DU702VH
(2)
Parameter
Default
Module
Term
MDF-DU502VH
MDF-DU702VH
Range
Comp. control
Set temp.
-80
℃
-80
℃
-50
℃
~
-90
℃
Control mode
Auto
Auto
fix
Comp. first start delay
time
3 min
3 min
3 min
~
15 min
Comp. restart delay time
3 min
3 min
fix
ON point
+0.5
℃
+0.5
℃
fix
OFF point
-0.5
℃
-0.5
℃
fix
Offset value
+1.0
℃
+1.0
℃
fix
Ambient temp.correct
-1.0
℃
-1.0
℃
fix
ON/OFF adjustment
value
existance
existance
fix
FAN control
Control mode
AUTO
AUTO
Control modes
ON point
27
℃
27
℃
-20
℃
~
40
℃
OFF point
26
℃
26
℃
fix
Capi heater
control
Control ON/OFF
ON
ON
ON, OFF
Control mode
OFF
OFF
ON, OFF, AUTO
Maximum cooling time
60 min
60 min
fix
Action interval
Every 18 hour
Every 18 hour
fix
AIP heater
control
Control ON/OFF
ON
ON
ON, OFF
ON point
-40
℃
-40
℃
-50
℃
~
10
℃
OFF point
ON point+1
℃
ON point+1
℃
fix
※
1 Configurable on service menu