1.3
Refrigerant release
Preparation
:
Refrigerant protection equipment (leather gloves, goggles), tools
Procedure
:
※
Wearing leather gloves and goggles because it handles refrigerant.
※
Confirm whether there are ignitable ones like electric appliances outdoors.
Install a piercing tool in the high / low pressure service pipe of the product, open the
valve of the dedicated GM (however, VR is not opened), and release the refrigerant
from the long hose to the outdoor.
(
Valve open
:VC
⇒
VG
⇒
VL
⇒
VH)
Note
:
Piercing tool is unnecessary if service valve is attached.
Place the detector near the tip of the outdoor long hose. Be sure to use a detector that
can detect HC refrigerant.
Make sure that the release refrigerant is almost gone by the guidelines and detectors of
the dedicated GM.
Open
Shut
VC
○
VG
○
VL
○
VH
○
VR
○
Valve state
High temperature H side
Pipe position of MDF-DU702VH
Low temperate H side
High temperature L side
Low temperature L side
To Outdoor
Long hose
Piercing tool
Low pressure side
service pipe
High pressure side
service pipe
Charge hose
VR
VG
VL
VC
VH
Refrigerant port
Vacuum port
High pressure port
Loew pressure
port
Dedicated GM
-39-