Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
122
28.6
Display current consumption COM-loop
(H5/A5)
The resolution is not very high, i.e. the displayed values give only a
rough idea of the current consumption.
The current consumption (an average value) for each COM loop can
be displayed.
NOTE!
No or very small current consumption can not be presented
correctly / precisely.
Action
Text in display
Comments
"Menu"
According to chapter
"Access code for service /
maintenance (H5 and
H8)", see page 116.
"
↵
"
A1 Calibration of supervised outputs
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
Scroll to menu A5
A5 Display current consumption on COM-loop
"
↵
"
Display current consumption on
COM-loop:
0
, control unit: 00
(press
↵)
Write loop number and
control unit number and
press "
↵
".
"
↵
"
Wait......
No reply from control unit.....
If the control unit don't
exist or don't answer.
Current consumption on COM-loop: 0 control unit
00 is xxxx mA
The current consumption
accuracy is ±5 mA.
"
↵
" or "ESC"
A5 Display current consumption on COM-loop
Scroll to another menu or
press "
ESC
".