Operating Instructions Fire alarm system EBL512 G3, V1.1.x
138
Power off / Power on
or
after 5 min.
FAULT: Restart control unit nn, code xx
,
address yyyyyyyyyy
yyyy-mm-dd hh:mm
After a restart / power on
(see page 81), there will
always be a fault
generated. The code will
be 00 and the address 0.
This fault has to be
acknowledged, see chapter
"FAULT Acknowledge
(H6)", page 126.
NOTE!
Before the very first
safe shut down
the Flash ROM is empty. Then
every time
safe shut down
is performed the valid data will be saved in
the Flash ROM, i.e. any old data will be overwritten.
When the c.i.e. is powered up, the data stored in the Flash ROM will
be used.
WARNING!
If
safe shut down
is
not
performed just before a c.i.e. power down,
then by power on the Flash ROM might be empty or the stored data
might be old / not valid.