Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
148
32.4
Disable interlocking output (H9/C4)
Interlocking outputs (Type = Interlocking) can be individually
disabled via this menu but not via menu H2/B3.
All
interlocking outputs can be collectively disabled via menu H2/B7.
The "Interlocking Combination" (Area / Point) is to be entered to
disable the output. Up to 200 interlocking outputs can be disabled.
Disabled interlocking outputs are listed in menu H4/U1 from which it
is also possible to get a print-out.
The LED
Fault / Disablements
"General disablements" (L10) is also
indicating one or more disabled interlocking outputs.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 85.
Scroll to menu H9.
H9 Interlocking outputs and inputs
"
↲
"
C1 Activated interlocking outputs / inputs
C2 Activate interlocking output
C3 Reset interlocking output
C4 Disable interlocking output
C5 Re-enable interlocking output
Scroll to menu C4.
C4 Disable interlocking output
"
↲
"
Disable interlocking output
area:
0
00 point: 00
(press
↵
)
Write the area number and
point and press
"
↲
".
If more interlocking
outputs shall be disabled
continue the same way.
Press "ESC" to menu C4.
"
↲
" (disable)
alt.
"ESC"
C4 Disable interlocking output
Scroll to another menu or
press "ESC".