Operating Instructions Fire alarm system EBL512 G3, V1.1.x
149
32.5
Re-enable interlocking output (H9/C5)
Disabled interlocking outputs are listed in menu H4/U1 from which it
is also possible to get a print-out.
Interlocking outputs (Type = Interlocking) can be re-enabled via this
menu but not via menu H2/B6.
If a
ll
interlocking outputs have been collectively disabled via H2/B7
they have to be re-enabled via H2/B7.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 85.
Scroll to menu H9.
H9 Interlocking outputs and inputs
"
↲
"
C1 Activated interlocking outputs / inputs
C2 Activate interlocking output
C3 Reset interlocking output
C4 Disable interlocking output
C5 Re-enable interlocking output
Scroll to menu C5.
C5 Re-enable interlocking output
"
↲
"
Re-enable interlocking output
area
0
01 point 01
area 004 point 01
This is a list in which you
can scroll. If there are no
disabled outputs, menu C5
will not open.
Press "
↲
" to re-enable the
selected output.
Press "ESC" to menu C5.
"
↲
"
alt.
"ESC"
Re-enable interlocking output
area
0
04 point 01
Scroll to another menu or
press "ESC".