Operating Instructions Fire alarm system EBL512 G3, V1.1.x
153
36
Replacing a TLON connection
board and/or the Main board
By the TLON network programming, some unique data will be stored
in a memory on the 1590 TLON connection board and some will be
stored in a memory on the 5010 main board.
Replacing a TLON connection board 1590
After replacing the board, do "Replace", "Update" and "Save" in
TLON Manager.
Replacing a TLON connection board 1590 and also the Main
board 5010
After replacing the boards, do "Replace", "Update" and "Save" in
TLON Manager.
Replacing the Main board 5010
After replacing the board, put back the TLON connection board(s) in
the same position as on the replaced main board, do "Update" and
"Save" in TLON Manager.