Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
63
FAULT: No reply, external presentation unit
xx, control unit xx
FAULT: No reply, fire brigade panel xx,
control unit xx
Alert Annunciation Unit 1735 / 1736.
External Presentation Unit 1728
External Fire Brigade Panel 1826 / 1828
The contact with the unit is interrupted. Check the cable, all
connections,etc. Is correct / complete SSD downloaded (via
WinG3)? Check the address and SW mode settings.
If there is a program memory fault in the unit, there will be a
fault message in the unit's display:
"Memory fault in
program area (n)"
(n=1 or 2). The unit will not work.
FAULT: No reply, expansion board x,
control unit xx
Valid for the 8 zones exp. board 4580, the 8 relays exp. board 4581
and the Inputs and outputs exp. board 4583, mounted in the control
unit no. xx.
EBL512 G3 cannot communicate with the board. Check / change the
address. Check the cables / connections.
FAULT: Printer, control unit xx
This is valid for an EBL512 G3, type 5000 with printer. Control unit
no. xx.
Faulty printer
Printer not correctly connected.
No paper.
FAULT: Read/write site data (SSW),
control unit xx
SSW = the data that is changed during operation, i.e. week average
sensor values, access codes, calibration values and event logs, in
control unit no. xx.
If the C.U. was made powerless (i.e. mains and battery
disconnected) without first doing a Safe shut down of control
unit via menu H8/S6 (see page 137), this fault might be
generated when the C.U. is powered again. After fault
acknowledge the SSW will get default values and the fault
will be corrected (serviced). Supervised outputs have to be