Operating Instructions Fire alarm system EBL512 G3, V1.1.x
68
FAULT: Wrong type, expansion board x,
control unit xx
Valid for the 8 zones exp. board 4580, the 8 relay outputs exp. board
4581 and the Inputs and outputs exp. board 4583, mounted in control
unit no. xx.
Check the type of board, which should be the same as programmed
via WinG3.
FAULT: Wrong type of unit zone: xxx
address: xx
technical number xxxxxx
Check the type of unit, which should be the same as programmed via
WinG3.
FAULT: Zone line input, xxx-xx
input x, expansion board x, CU xx
Valid for the 8 zones exp. board 4580 zone line input x (xxx-xx =
zone – address). The board is mounted in control unit xx.
Break on the zone line, wrong / no end-of-line device / short-circuit (if
not programmed for fire alarm at short-circuit).
FAULT: Zone line input, zone: xxx address:
xx
technical number xxxxxx
Valid for the Multipurpose I/O unit 3361 monitored zone line input Z.
Break on the zone line or wrong / no end-of-line capacitor (470 nF) or
short-circuit (if not programmed for fire alarm at short-circuit).
No contact with main board
Shown only in the affected control unit.
Fault in the Main board 5010 software or hardware. Check the cable
between the Main board and MMI board. This is a very serious fault.
Call for service personnel/engineer immediately.
(User programmable text; External fault)
Programmable input is connected to any external equipment's fault
output. User definable fault message programmed via WinG3.