Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
92
25.2
Disable zone / address (H2/B2)
Addressable alarm points (also addressable manual call points),
connected to the COM loop, can be individually disabled.
Disabled alarm points, zone / addresses, are listed in menu H4/U1
from which it is also possible to get a print-out.
Regarding disabled analog smoke detector: The sensor values will not
be saved, i.e. only the values saved before and after the disablement
will be used when calculating the week average sensor value.
Disabled alarm points, zone / addresses, have to be re-enabled via
menu H4/B2.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 85.
Scroll to menu H2.
H2 Disable or re-enable
"
↵
"
B1 Disable zone
B2 Disable zone / address
B3 Disable output
B4 Re-enable zone
B5 Re-enable zone / address
B6 Re-enable output
B7 Disable / re-enable output type
B8 Disable / re-enable alarm devices
B9 Disable / re-enable routing equipment
B10 De-activate alert annunciation function
Scroll to menu B2.
B2 Disable zone / address
"
↵
"
Disable zone:
0
00 address: 00
(press
↵)
Write zone number and
the address (e.g. 001
and 01)
Disable zone: 001 address
0
1
(press
↵)
Press "
↲
" to disable.
"
↵
"
Re-enable time:
H
H:MM
No
Yes
(Default is current time + 3 hours)
Press "
↲
" to disable
without automatic re-
enablement.
or
Accept the time (+ 3
hours) or set another
time (max + 24 hours),
select "Yes" and press
"
↲
" to disable with
automatic re-
enablement.