Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
94
25.3
Disable output (H2/B3)
All outputs (
except outputs type "Alarm device"
) can be
individually disabled. Disabled output will stay in (or return to) the
normal condition for the output respectively.
Disabled outputs are listed in menu H4/U1 from which it is also
possible to get a print-out.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 85.
Scroll to menu H2.
H2 Disable or re-enable
"
↵
"
B1 Disable zone
B2 Disable zone / address
B3 Disable output
B4 Re-enable zone
B5 Re-enable zone / address
B6 Re-enable output
B7 Disable / re-enable output type
B8 Disable / re-enable alarm devices
B9 Disable / re-enable routing equipment
B10 De-activate alert annunciation function
Scroll to menu B3.
B3 Disable output
"
↵
"
Disable output type:
3361/3364
S
R
Expansion board
Select output type.
S
=CU voltage output S0-S3.
R
=CU relay output R0-R1.
Press "
↵
" to accept.
"
↵
"
Depending on the
selected type the
following will be
shown:
Disable
0
00000 output 0
(press
↵)
Write the data
for the
output respectively.
Press "
↵
" to accept.
LED
Fault / Disablements
"General disablements"
(L10) will light up.
Disable CU:
0
0 S: 0
(press
↵)
Disable CU:
0
0 R: 0
(press
↵)
Disable control unit:
0
0 exp. board: 0 output: 0
"
↵
"
Disable output type:
3361/3364
S
R
Expansion board
Disable another output or
press "
ESC
". Scroll to
another menu or press
"
ESC
".