15
1-12. Optional Distribution Joint Kits
See the installation instructions packaged with the distribution joint kit for the installation procedure.
Table 11
Model name
Cooling capacity
after distribution
Remarks
1. CZ-P160BK2
22.4 kW or less *
For indoor unit
* In case the total capacity of indoor units connected after distribution exceeds the capacity of the outdoor unit, select the distribution
tubing size for the capacity of the outdoor unit.
■
Tubing size (with thermal insulation)
1. CZ-P160BK2
Use: Total capacity of indoor units after distribution joint is 22.4 kW or less.*
Example:
110
97
110
97
72
72
B
A
D
B
B
C
C
C
D E
A
C
D
E
C
Table 12 : Size of connection point on each part (Shown are inside diameters of tubing)
Size
Part A
Part B
Part C
Part D
Part E
mm
ø19.05
ø15.88
ø12.7
ø9.52
ø6.35
*
In case the total capacity of indoor units connected after distribution exceeds the capacity of the outdoor unit, select the distribution
tubing size for the capacity of the outdoor unit.
Unit: mm
Distribution
Joint
Insulation
Distribution
Joint
Insulation
Gas tube
Liquid tube